4 TROUBLESHOOTING
4.6 Event List
Operation
00C11
<<Another station>> Data link stop (cyclic
transmission stopped)
Data link of another station was stopped.
00C20
<<Another station>> Parameter error occurrence
An parameter error has occurred in another station.
00C21
<<Another station>> Error occurrence
An error has occurred in another station.
00C22
Station already in use
Master station/submaster station duplication, or station No. overlap has occurred in the
network.
00C24
<<Another station>> Receive frame error
occurrence
A receive frame error has occurred at another station.
00C25
Receive parameter error occurrence
A parameter error received from the master station or control station has been detected.
00C27
Transient reception failed
Frequency of transient transmission to the own station is too high and transient
reception failed.
00C28
<<Own station>> Receive frame error line status
warning level
A receive frame error (line status: warning level) has been occurred.
00C29
<<Another station>> Receive frame error line status
warning level
A receive frame error (line status: warning level) has been occurred.
Event code Overview
Cause
24000
Data link startup instruction
Data link startup to the own station or another station was instructed.
24001
Data link stop instruction
Data link stop to the own station or another station was instructed.
24010
Temporary error invalid station setting instruction
Temporary error invalid station setting was instructed to the slave station.
24011
Temporary error invalid station cancel instruction
Temporary error invalid station cancel was instructed to the slave station.
24020
Reserved station cancel setting instruction
Reserved station cancel setting was instructed to the slave station.
24021
Reserved station enable setting instruction
Reserved station enable setting was instructed to the slave station.
24030
The network No., station No. setting/change
instruction execution
Setting or change of the network No. or station No. was instructed to the slave station.
24100
<<Own station>> Parameter change/new
parameter acceptance
Parameter was changed. Or new parameter was received at power-on.
24F00
<<Another station>> CPU operating status change
detection
Operating status of the programmable controller CPU on another station was changed.
Event code Overview
Cause
Summary of Contents for RD77GF16