2 PARAMETER SETTINGS
2.3 Basic Settings
73
2
Precautions
■
Device set to "CPU Side"
Set a device range not to overlap the one used for the following:
• "Refresh Settings" in "Basic Settings" of other network modules
• "Link Refresh Settings" in "Basic Settings" of a CC-Link master/local module
• I/O Nos. used for I/O modules and intelligent function modules
• "Refresh settings" of intelligent function modules
• "Refresh Setting between Multiple CPUs" of "CPU Parameter" for a multiple CPU system
■
Link refresh range
• Set only link devices used in the CPU module for link refresh range. Doing so will reduce link refresh points, resulting in a
shorter link refresh time.
• Do not include RWw of the servo amplifier (motion mode) in the link refresh range. The error "Network refresh setting error"
(error code: 3065H) occurs and the READY signal [X0] is not turned ON.
• When the inter-module synchronization setting is set to "Not Use", the link device (RX/RY/RWr/RWw) of the station whose
network synchronous communication is set to "Synchronous" is not refreshed.
When the software version of the Simple Motion module is "Ver.05":
When the control CPU is a safety CPU, the refresh setting of RWw of the servo amplifier (motion mode) is not
checked.
Do not include RWw of the servo amplifier (motion mode) in the refresh range. If it is included, the operation
will be failure such as that the servo ON is not executed.
■
Changing link device assignment in "Network Configuration Settings" of "Basic Settings"
Correct the set range in "Refresh Settings" of "Basic Settings".
Network Topology
Select the topology type according to the actual network configuration.
Item
Description
Setting range
Network Topology
The topology type is fixed to "Line/Star".
Summary of Contents for RD77GF16
Page 1: ...MELSEC iQ R Simple Motion Module User s Manual Network RD77GF4 RD77GF8 RD77GF16 RD77GF32 ...
Page 2: ......
Page 181: ...I 179 MEMO ...
Page 185: ......