Check code
5300
(UH)
Current sensor trouble
Abnormal points and detection methods
Causes and checkpoints
If the detected current sensor input value (primary current) during
compressor operation is outside the specified range.
Decrease/trouble of power supply voltage
Disconnection of compressor wiring
Input sensor trouble on outdoor power circuit board
●Diagnosis of defects
Make sure to turn the power OFF before connecting/disconnecting
any connectors, or replacing boards.
Diagnosis
Remedy
No
No
Yes
Yes
Does it satisfy the condition 1(*)
in the lower right?
Is there any abnormality such as
disconnection or looseness?
The power supply voltage is decreased or
abnormal.
Check the power supply facility.
Connect the compressor wiring properly.
Replace the outdoor power circuit board
(Malfunction of current sensor circuit).
Check the input current at the time of
abnormal stop.
Check the compressor wiring for
disconnection or looseness.
Error detecting condition
34 A or more for 10 consecutive
seconds, or 38 A or more
Model
Single phase model
Condition 1:
*Applicable only for
single phase model.