97
TCH091
8-6. HOW TO CHECK THE PARTS
Parts name
Checkpoints
Thermistor (TH2)
<HIC Pipe>
Thermistor (TH3)
<Outdoor Liquid Pipe>
Thermistor (TH4)
<Compressor>
Thermistor (TH6)
<Suction Pipe>
Thermistor (TH7)
<Ambient>
Thermistor (TH8)
<Heat Sink>
Disconnect the connector then measure the resistance with a multimeter.
(At the ambient temperature 10 to 30°C)
Normal
Abnormal
TH4
160 to 410 kΩ
Open or short
TH2
TH3
TH6
TH7
4.3 to 9.6 kΩ
TH8
39 to 105 kΩ
Fan motor (MF1, MF2)
Refer to the next page.
Solenoid valve coil
<4-way valve>
(21S4)
Measure the resistance between the terminals with a multimeter.
(At the ambient temperature 20°C)
Normal
Abnormal
2085 ± 208.5 Ω
Open or short
Motor for compressor
(MC)
Measure the resistance between the terminals with a multimeter.
(Winding temperature 20°C)
Normal
Abnormal
0.265 ± 0.013 Ω
Open or short
Solenoid valve coil
<Bypass valve> (SV1)
<Oil return valve> (SV3)
Measure the resistance between the terminals with a multimeter.
(At the ambient temperature 20°C)
Normal
Abnormal
1182.5 ± 83 Ω
Open or short
Linear expansion Valve
(LEV-A)
Normal
Abnormal
Gray - Black
Gray - Red
Gray - Yellow
Gray - Orange
Open or short
46 ± 3 Ω
Linear expansion Valve
(LEV-B)
Normal
Abnormal
Red - White
Red - Orange
Red - Yellow
Red - Blue
Open or short
46 ± 4 Ω
W
V
U
1
2
3
4
5
M
Red
Blue
Orange
Yellow
White
1
2
3
4
5
M
Gray
Orange
Red
Yellow
Black