124
TCH091
10-2. PRECAUTIONS AGAINST REFRIGERANT LEAKAGE
Indoor unit
Branch header
Opening
Wall
Outdoor unit
(Situation in which there
are no door openings or
in which there are open-
ings above and below
doors that occupy at
least 0.15% of the floor
area)
Indoor unit
Branch header
Outdoor unit
10-2-1. Introduction
R410A refrigerant of this air conditioner is non-toxic and non-flammable but leaking of large amount from an indoor unit into
the room where the unit is installed may be deleterious. To prevent possible injury, the rooms should be large enough to keep the
R410A concentration specified by ISO 5149-1 as follows.
Note:
When the air conditioning system consists of several independent refrigerant system, figure out the total refrigerant
amount by each independent refrigerant system.
Follow (1) to (3) to confirm the R410A concentration and take appropriate treatment, if necessary.
(1) Calculate total refrigerant amount by each refrigerant system. Total refrigerant amount is precharged
refrigerant at ex-factory plus additional charged amount at field installation.
(2) Calculate room volumes (m
3
) and find the room with the smallest volume
The part with represents the room with the smallest volume.
Indoor unit
All refrigerant of this system will leak out to this
room if there is leakage at this indoor unit.
Direction
of refrigerant flow
Outdoor unit
Branch header
Maximum concentration
Maximum refrigerant concentration of R410A of a room
is 0.44kg/
K
accordance with ISO 5149-1.
To facilitate calculation, the maximum concentration is
expressed in units of kg/
K
( kg of R410A per
K
)
(ISO 5149-1)
Maximum concentration of R410A: 0.44
kg
/
K
10-2-2. Confirming procedure of R410A concentration
(b) There are partitions, but there are openings that allow
the effective mixing of air.
(a) Situation in which there are no partitions
Indoor unit
The smallest
room
The second
smallest room
Outdoor unit
Ventilation apparatus
Branch header
(c) If the smallest room has mechanical ventilation apparatus that is linked to a household gas detection and alarm
device, the calculations should be performed for the second smallest room.
Total refrigerant in the refri
gerating unit (kg)
[
Ma
ximum concentration(kg/
K
)*
The smallest room in which an indoor
unit has been installed (
K
)
*Maximum concentration of R410A:0.44kg/
K
(3) Use the results of calculations (1) and (2) to calculate the refrigerant concentration:
If the calculation results do not exceed the maximum concentration, perform the same calculation for larger rooms
until it has been determined that nowhere exceeds the maximum concentration.
Summary of Contents for PUMY-P250YBM2-BS
Page 23: ...23 TCH091 6 WIRING DIAGRAM ...
Page 155: ......