130
TCH091
OPERATING PROCEDURE
PHOTOS/FIGURES
15. Removing the Compressor protector (TRS)
(1) Remove the service panel. (See Photo 1)
(2) Remove the top panel. (See Photo 1)
(3) Remove the cover panel front. (See Photo 1)
(4) Remove the cover panel rear. (See Photo 1)
(5) Remove the side panel R. (See Photo 1)
(6) Pull out the lead wire of high pressure switch and
disconnect the connector, 63H (yellow) from the multi con
-
troller board in the electrical parts box. (See Photo 11)
(7) Remove the comp felt covering the compressor.
(See Photo 13)
(8) Loosen the clamp or band for the lead wire of the electrical
parts box and separator.
(9) pull out the Compressor protector (TRS) from the holder.
(See Photo 16)
Holder
Compressor protector (TRS)
Photo 16