21
TCH091
PUMY-P300YBM2
PUMY-P250YBM2
1.5m
1m
MICROPHONE
UNIT
GROUND
4-5. NOISE CRITERION CURVES
OCT
AVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
BAND CENTER FREQUENCIES, Hz
90
80
70
60
50
40
30
20
10
63
125
250
500 1000 2000 4000 8000
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
COOLING
MODE
HEATING
55
SPL(dB)
61
LINE
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
Operation
PUMY-P250YBM2
PUMY-P300YBM2
Operating
conditions
Ambient
temperature
Indoor
DB/
WB
27°C/19°C
20°C/ —
27°C/19°C
20°C/—
Outdoor
35°C/24°C
7°C/6°C
35°C/24°C
7°C/6°C
Indoor unit
No. of connected units
Unit
4
5
No. of units in operation
4
5
Model
—
63 x 4
63 x 4 + 50 x 1
Piping
Main pipe
m
5
5
Branch pipe
5
5
Total pipe length
25
30
Fan speed
—
Hi
Hi
Amount of refrigerant
kg
13.6
14.9
Outdoor unit
Electric current
A
12.85
12.30
18.99
14.59
Voltage
V
380
380
Compressor frequency
Hz
63
76
82
87
Pressure
High pressure/Low pressure
MPa
3.09/0.98
2.30/0.60
3.40/0.90
2.30/0.61
Temp. of
each section
Outdoor
unit
Discharge
°C
72.3
57.9
81.8
62.4
Heat exchanger outlet
38.9
7.1
40.4
5.9
Accumulator inlet
9.9
− 1.1
8.4
− 2.2
Compressor inlet
12.0
− 1.7
9.3
− 3.0
Indoor unit LEV inlet
26.0
24.8
31.8
20.9
Heat exchanger inlet
13.2
31.1
13.3
25.6
4-6. STANDARD OPERATION DATA (REFERENCE DATA)
OCT
AVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
BAND CENTER FREQUENCIES, Hz
90
80
70
60
50
40
30
20
10
63
125
250
500 1000 2000 4000 8000
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
COOLING
MODE
HEATING
57
SPL(dB)
62
LINE
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE