Check code
1500
(U7)
Superheat due to low discharge temperature trouble
●Diagnosis of defects
Make sure to turn the power OFF before connecting/disconnecting any connectors, or replacing boards.
Diagnosis
Remedy
Chart 2 of 2
Is the resistance detected?
Replace the indoor LEV.
No
No
Yes
Yes
No
Yes
Continued from the previous page.
Is the voltage normal?
Is it free from any trace of over-
heating or burning?
Is the voltage detected?
Replace the indoor controller board.
Replace the 63HS.
Replace the outdoor multi controller circuit
board.
Check the voltage and appearance of the
indoor controller board.
Check the 63HS voltage.
50
51
TCH091