27
TCH091
Branch box
Port A
Port B
Port C
Port D
Port E
Branch box pipe size
A
Model
Liquid pipe
Gas pipe
P250
ø9.52*
ø22.2
ø22.2
P300
ø12.7
B, C, D, E
Total down-stream capacity
of indoor units
Model
Liquid pipe
Gas pipe
– 16.0 kW
P250
ø9.52*
ø15.88
P300
ø12.7
16.1 kW – 22.4 kW
P250
ø9.52*
ø19.05
P300
ø12.7
22.5 kW –
P250
ø9.52*
ø22.2
P300
ø12.7
2-branch joint
CMY-Y62-G-E
4-branch header
CMY-Y64-G-E
8-branch header
CMY-Y68-G-E
Different-diameter joint (optional parts) (Fig. 7-2, 7-3)
Model name
Connected pipes diameter
Diameter A
Diameter B
mm
mm
mm
MAC-A454JP
ø9.52 →
ø12.7
ø9.52
ø12.7
MAC-A455JP
ø12.7 →
ø9.52
ø12.7
ø9.52
MAC-A456JP
ø12.7 →
ø15.88
ø12.7
ø15.88
PAC-493PI
ø6.35 →
ø9.52
ø6.35
ø9.52
PAC-SG76RJ-E
ø9.52 →
ø15.88
ø9.52
ø15.88
PAC-SG75RJ-E
ø15.88 →
ø19.05
ø15.88
ø19.05
PAC-SG71RJ-E
ø15.88 *1
→
ø22.2 *2
ø15.88 *1
ø22.2 *2
*1 When connecting to MSDD-50AR-E or a branch box,
the pipes on-site.
Use the nuts that are included with the 2-branch pipe and branch box.
*2 Brazing
2 branch pipe (Joint) : Optional parts (According to the connection method,
you can choose the favorite one.)
Model name
Connection method
MSDD-50AR-E
MSDD-50BR-E
brazing
A
A
E
B
C
C
D
D
a
b
c
d
e
f
g
h
i
j
E
E
E
E
E
F
F
F
F
F
A
Outdoor unit
B
First joint
C
Branch header
D
Branch box
E
CITY MULTI Indoor unit
F
M series Indoor unit
Fig. 7-4
(1) Valve size of branch box for outdoor unit
For liquid
ø9.52 mm
For gas
ø15.88 mm
(2) Valve size of branch box for indoor unit
A
UNIT
Liquid pipe
ø6.35 mm
Gas pipe
ø9.52 mm
B
UNIT
Liquid pipe
ø6.35 mm
Gas pipe
ø9.52 mm
C
UNIT
Liquid pipe
ø6.35 mm
Gas pipe
ø9.52 mm
D
UNIT
Liquid pipe
ø6.35 mm
Gas pipe
ø9.52 mm
E
UNIT
Liquid pipe
ø6.35 mm
Gas pipe
ø12.7 mm
* 3-branch type : only
A
,
B
,
C
unit
* ø12.7 when connecting the indoor unit for PEFY-P200 or P250
a, b, c – j
Indoor unit series
Model number
Liquid pipe
Gas pipe
kW
cal
City Multi
– 50
–
ø6.35
ø12.7
63 – 140
–
ø9.52
ø15.88
200
–
ø19.05
250
–
ø22.2
M series
– 35
– 32
ø6.35
ø9.52
50
–
ø12.7
–
50
ø15.88
60 –
63 –
ø9.52
ø15.88
S series
– 35
–
ø6.35
ø9.52
50 – 60
–
ø12.7
–
–
ø15.88
71 –
–
ø9.52
ø15.88
7-2-3. Mixed system (CITY MULTI indoor units and M series indoor units [Via Branch box])
Summary of Contents for PUMY-P250YBM2-BS
Page 23: ...23 TCH091 6 WIRING DIAGRAM ...
Page 155: ......