3. Piping Design
3 - 22
S.D. WR2
MEE15K052
1. Refrigerant and water pipe size
(1) Refrigerant pipe between heat source unit and HBC controller (Part A, A1, A2, and A3)
(2) Water pipe between HBC controller and indoor units (Sections a, b, c, d, e, and g)
*Water Pipe size between HBC controller and joint is also 20A.
(3) Water pipe between HBC controller and Sub-HBC
(4) Refrigerant pipe between HBC controller and HBC controller
2. Connecting the HBC controller
(1) Size of the pipe that fits the standard HBC controller ports
Indoor unit
Inlet pipe size
Outlet pipe size
P15 - P50
20A
20A
Inlet pipe size
Outlet pipe size
Cold-water side
20A
20A
Hot-water side
20A
20A
Unit: mm [inch]
ø15.88 [5/8"] (Brazed connection)
HBC CONTROLLER
Unit model
Model name
Use of one HBC controller
Use of two HBC controllers
High pressure side
Low pressure side
PQRY-P200
(HBC CONTROLLER)
CMB-WP108V-GA1
CMB-WP1016V-GA1
*1
ø19.05 (Brazing)
ø22.2 (Brazing)
PQRY-P250
ø22.2 (Brazing)
PQRY-P300
ø28.58 (Brazing)
ø15.88 (Brazing)
ø19.05 (Brazing)
ø19.05 (Brazing)
ø19.05 (Brazing)
PQRY-P350
Heat source unit side
Unit model
Model name
High pressure side
Between outdoor unit and twining pipe
Between twining pipe and HBC
Low pressure side
(HBC CONTROLLER)
CMB-WP108V-GA1
CMB-WP1016V-GA1
*1
ø22.2 (Brazing)
PQRY-P300
ø28.58 (Brazing)
PQRY-P350
ø28.58 (Brazing)
ø28.58 (Brazing)
ø28.58 (Brazing)
High pressure side
ø15.88 (Brazing) for each HBC
ø15.88 (Brazing) for each HBC
ø15.88 (Brazing) for each HBC
ø19.05 (Brazing) for each HBC
ø19.05 (Brazing) for each HBC
Low pressure side
ø19.05 (Brazing) for each HBC
ø19.05 (Brazing) for each HBC
ø19.05 (Brazing) for each HBC
ø22.2 (Brazing) for each HBC
ø22.2 (Brazing) for each HBC
ø19.05 (Brazing)
ø19.05 (Brazing)
ø22.2 (Brazing)
ø22.2 (Brazing)
ø22.2 (Brazing)
PQRY-P400
PQRY-P450
PQRY-P500
HBC CONTROLLER
Heat source unit side
*1. PQRY-P400YLM model or larger requires a connection of two main-HBC controllers in parallel.
(E)
(E)
(E)
(E)
(E)
(E)
(E)
(E)
(G)
(A)
(B)
(F)
*1
(C)
(D)
(A) To heat source unit
(B) End connection (brazing)
(C) Main-HBC controller
(D) Sub-HBC controller
(E) Indoor unit
(F) Twinning pipe (field supply)
(G) Up to three units for 1 branch hole; total capacity: below 80 (but same in cooling/heating mode)
Note:
1) To connect multiple indoor units to a port
• Maximum total capacity of connected indoor units: P80 or below
• Maximum number of connectable indoor units: 3 units
• Branch joints are field-supplied.
All the indoor units that are connected to the same port must be in the same group and Thermo-ON/OFF
operation simultaneously. For all the indoor units in the group, the room temperature needs to be monitored
via the connected remote controller.
0000003907.BOOK 22 ページ 2016年2月18日 木曜日 午前10時53分
Summary of Contents for PLFY-WP VBM-E
Page 3: ...MEE15K052 ...
Page 5: ...1 2 MEE15K052 ...
Page 39: ...1 36 MEE15K052 ...
Page 63: ...1 60 MEE15K052 ...
Page 79: ...1 76 MEE15K052 ...
Page 89: ...1 86 MEE15K052 ...
Page 91: ...2 2 MEE15K052 ...
Page 125: ...2 36 MEE15K052 ...
Page 155: ...3 2 MEE15K052 ...
Page 169: ...3 16 MEE15K052 ...
Page 183: ...3 30 MEE15K052 ...