1 - 5
PEFY
MEE15K052
1. SPECIFICATIONS
Model
PEFY-WP40VMS1-E
PEFY-WP50VMS1-E
Power source
1-phase 220-230-240 V 50/60
Hz
1-phase 220-230-240 V 50/60
Hz
Cooling capacity
*1 kW
4.5
5.6
(Nominal)
*1 kcal/h
3,900
4,800
*1 BTU/h
15,400
19,100
*2 Power input
kW
0.090
0.090
*2 Current input
A
0.73
0.77
Heating capacity
*3 kW
5.0
6.3
(Nominal)
*3 kcal/h
4,300
5,400
*3 BTU/h
17,100
21,500
*2 Power input
kW
0.070
0.070
*2 Current input
A
0.62
0.66
External finish
Galvanized steel plate
Galvanized steel plate
External dimension H x W x D
mm
200 x 990 x 700
200 x 1,190 x 700
in.
7-7/8 x 39 x 27-9/16
7-7/8 x 46-7/8 x 27-9/16
Net weight
kg (lbs)
25 (56)
27 (60)
Heat exchanger
Cross fin (Aluminum fin and
copper tube)
Cross fin (Aluminum fin and
copper tube)
Water Volume
L
1.0
1.7
FAN
Type x Quantity
Sirocco fan x 3
Sirocco fan x 4
*4 External static press.
Pa
<5> - 15 - <35> - <50>
<5> - 15 - <35> - <50>
mmH
2
O
<0.5> - 1.5 - <3.6> - <5.1>
<0.5> - 1.5 - <3.6> - <5.1>
Motor Type
DC motor
DC motor
Motor output
kW
0.096
0.096
Driving mechanism
Direct-driven by motor
Direct-driven by motor
Air flow rate
(Low-Mid-High)
(Low-Mid-High)
m
3
/min
9.5 - 11.0 - 13.0
12.0 - 14.0 - 16.5
L/s
158 - 183 - 217
200 - 233 - 275
cfm
335 - 388 - 459
424 - 494 - 583
Sound pressure level (measured in anechoic room)
(Low-Mid-High)
(Low-Mid-High)
*2 dB <A>
30-32-35
30-33-36
Insulation material
EPS, Polyethylene foam, Ure-
thane foam
EPS, Polyethylene foam, Ure-
thane foam
Air filter
PP honeycomb fabric.
PP honeycomb fabric.
Protection device
Fuse
Fuse
Refrigerant control device
-
-
Connectable outdoor unit/HBC controller
CITY MULTI YLM series/
CMB-WP-V-GA1, CMB-WP-
V-GB1
CITY MULTI YLM series/
CMB-WP-V-GA1, CMB-WP-
V-GB1
Water piping diameter
Inlet
in.
Rc 3/4 screw
Rc 3/4 screw
*5 *6 Outlet
in.
Rc 3/4 screw
Rc 3/4 screw
Field drain pipe size
mm (in.)
O.D.32 (1-1/4)
O.D.32 (1-1/4)
Drawing
External
KD94T794X01
KD94T794X01
Wiring
KD94T793X01
KD94T793X01
Refrigerant cycle
-
-
Standard attachment
Document
Installation Manual, Instruc-
tion Book
Installation Manual, Instruc-
tion Book
Accessory
Insulation pipe for water pipe,
Washer, Drain hose, Tie band
Insulation pipe for water pipe,
Washer, Drain hose, Tie band
Optional parts
Control box replace kit
PAC-KE70HS-E
PAC-KE70HS-E
Remarks
Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be referred
to the Installation Manual.
Due to continuing improvement, above specifications may be subject to change without notice.
Notes:
Unit converter
1.Nominal cooling conditions
Indoor: 27°CD.B./19°CW.B. (81°FD.B./66°FW.B.), Outdoor: 35°CD.B. (95°FD.B.)
Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
2.The values are measured at the factory setting of external static pressure.
3.Nominal heating conditions
Indoor: 20°CD.B. (68°FD.B.), Outdoor: 7°CD.B./6°CW.B. (45°FD.B./43°FW.B.)
Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
4.The factory setting of external static pressure is shown without < >.
Refer to "Fan characteristics curves", according to the external static pressure, in DATA BOOK for the usable
range of air flow rate.
5.Be sure to install a valve on the water outlet.
6.Install a strainer (40 mesh or more) on the pipe next to the valve to remove the foreign matters.
7.Please group units that operate on 1 branch.
kcal/h =kW x 860
BTU/h =kW x 3,412
cfm
=m
3
/min x 35.31
lbs
=kg/0.4536
*Above specification data is
subject to rounding variation.
0000003897.BOOK 5 ページ 2016年1月13日 水曜日 午前10時19分
Summary of Contents for PLFY-WP VBM-E
Page 3: ...MEE15K052 ...
Page 5: ...1 2 MEE15K052 ...
Page 39: ...1 36 MEE15K052 ...
Page 63: ...1 60 MEE15K052 ...
Page 79: ...1 76 MEE15K052 ...
Page 89: ...1 86 MEE15K052 ...
Page 91: ...2 2 MEE15K052 ...
Page 125: ...2 36 MEE15K052 ...
Page 155: ...3 2 MEE15K052 ...
Page 169: ...3 16 MEE15K052 ...
Page 183: ...3 30 MEE15K052 ...