2 - 21
R2
MEE15K052
2. CAPACITY TABLES
P200YLM-A1
25.0
85,300
7.08
P250YLM-A1
31.5
107,500
10.06
PURY-
Indoor unit temperature correction
Nominal
Heating
Capacity
Input
kW
BTU/h
kW
To be used to correct indoor unit capacity only
Indoor Temperature [°CD.B.]
Ratio of heating capacity
15
16
17
18
19
20
21
22
23
27
26
25
24
0.6
0.7
0.8
0.9
1.0
1.1
Outdoor unit temperature correction
1.1
0.9
0.8
0.7
0.6
0.5
1.0
1.2
Ratio of heating capacity
0.9
1.0
1.1
1.3
1.2
1.4
0.8
0.7
0.6
0.4
0.5
Ratio of power input
-20
-4
-15
5
-10
14
-5
23
0
32
5
41
10
50
15
59
°CW.B.
°FW.B.
Indoor Temperature
Indoor Temperature
Outdoor Temperature
-20
-4
-15
5
-10
14
-5
23
0
32
5
41
10
50
15
59
°CW.B.
°FW.B.
Outdoor Temperature
20°CD.B.
68°FD.B.
27°CD.B.
81°FD.B.
25°CD.B.
77°FD.B.
20°CD.B.
68°FD.B.
To be used to correct outdoor unit only
Outdoor unit power input is affected by the indoor and outdoor temperatures as shown in the graph above. Please consult the sales office for details.
15°CD.B.
59°FD.B.
EP200YLM-A1
25.0
85,300
6.92
EP250YLM-A1
31.5
107,500
9.84
PURY-
Nominal
Heating
Capacity
Input
kW
BTU/h
kW
0000003904.BOOK 21 ページ 2016年1月25日 月曜日 午後2時31分
Summary of Contents for PLFY-WP VBM-E
Page 3: ...MEE15K052 ...
Page 5: ...1 2 MEE15K052 ...
Page 39: ...1 36 MEE15K052 ...
Page 63: ...1 60 MEE15K052 ...
Page 79: ...1 76 MEE15K052 ...
Page 89: ...1 86 MEE15K052 ...
Page 91: ...2 2 MEE15K052 ...
Page 125: ...2 36 MEE15K052 ...
Page 155: ...3 2 MEE15K052 ...
Page 169: ...3 16 MEE15K052 ...
Page 183: ...3 30 MEE15K052 ...