3 - 5
S.D. R2
MEE15K052
2. M-NET control
2. M-NET control
2-1. Address setting
2-1-1. Rule of setting address
Unit
Indoor unit
ME, LOSSNAY
Remote controller
(Main)
ME, LOSSNAY
Remote controller
(Sub)
Address setting
01 ~ 50
52 ~ 99, 100
101 ~ 150
151 ~ 199, 200
Note
Example
The address of the smallest address of indoor unit
connected to the HBC cont50
Please reset one of them to an address between 51
and 99 when two addresses overlap.
The address automatically becomes "100" if it is set
as "01~ 50"
The smallest address of indoor unit in the group + 100
The place of "100" is fixed to "1"
ON/OFF remote
controller
AE-200E/AE-50E
EW-50E
AG-150A
AT-50B
EB-50GU-J
000, 201 ~ 250
000, 201 ~ 250
Local remote controller
System controller
The address of main remote cont 50
The address automatically becomes "200" if it is set
as "00"
10
1
10
1
0 1
2
3
4 5
6
7
8
9
0 1
2
3
4 5
6
7
8
9
10
1
10
1
0
1
2
3
4 5
6
7
8
9
0
1
2
3
4 5
6
7
8
9
0
1
2
3
4 5
6
7
8
9
0 1
2
3
4 5
6
7
8
9
10
1
0
1
2
3
4 5
6
7
8
9
0
1
2
3
4 5
6
7
8
9
0
1
2
3
4 5
6
7
8
9
10
1
100
10
1
100
LMAP04-E
201 ~ 250
1
1
Fixed
Fixed
2
Fixed
Outdoor unit
HBC controller
51 ~ 99, 100
The smallest address of indoor unit in same refrigerant
50
Assign sequential address numbers to the outdoor
units in one refrigerant circuit system. OC, OS1 and
OS2 are automatically detected. (Note 2)
Please reset one of them to an address between 51
and 99 when two addresses overlap.
The address automatically becomes "100" if it is set
as "01~ 50"
Use the most recent address within the same group of
indoor units.
0 1
2
3
4 5
6
7
8
9
0 1
2
3
4 5
6
7
8
9
0 1
2
3
4 5
6
7
8
9
0 1
2
3
4 5
6
7
8
9
0 1
2
3
4 5
6
7
8
9
0 1
2
3
4 5
6
7
8
9
10
1
(Note1)
0,2
0~5
0~9
PAC-YG50ECA
000, 201 ~ 250
10
1
100
0,2
0~5
0~9
BAC-HD150
000, 201 ~ 250
10
1
100
0,2
0~5
0~9
The smallest group No. to be managed is changeable.
Settings are made on the initial screen of AG-150A.
Settings are made with setting tool of BM ADAPTER.
The smallest group No. to be m 200
Note1: To set the address to "100", set it to "50"
Note2: Outdoor units OC, OS1 and OS2 in one refrigerant circuit system are automatically detected.
OC, OS1 and OS2 are ranked in descending order of capacity. If units are the same capacity, they are ranked in ascending
order of their address.
0000003906.BOOK 5 ページ 2016年2月18日 木曜日 午前10時34分
Summary of Contents for PLFY-WP VBM-E
Page 3: ...MEE15K052 ...
Page 5: ...1 2 MEE15K052 ...
Page 39: ...1 36 MEE15K052 ...
Page 63: ...1 60 MEE15K052 ...
Page 79: ...1 76 MEE15K052 ...
Page 89: ...1 86 MEE15K052 ...
Page 91: ...2 2 MEE15K052 ...
Page 125: ...2 36 MEE15K052 ...
Page 155: ...3 2 MEE15K052 ...
Page 169: ...3 16 MEE15K052 ...
Page 183: ...3 30 MEE15K052 ...