2 - 8
R2
MEE15K052
1. SPECIFICATIONS
Model
PURY-P500YLM-A1 (-BS)
Power source
3-phase 4-wire 380-400-415 V 50/60 Hz
Cooling capacity
*1 kW
56.0
(Nominal)
kcal/h
50,000
*1 BTU/h
191,100
Power input
kW
22.67
Current input
A
38.2-36.3-35.0
EER
kW/kW
2.47
Temp. range of
Indoor
W.B.
15.0~24.0°C (59~75°F)
cooling *3 Outdoor
D.B.
-5.0~46.0°C (23~115°F)
Heating capacity
*2 kW
58.0
(Nominal)
kcal/h
50,000
*2 BTU/h
197,900
Power input
kW
17.53
Current input
A
29.5-28.1-27.0
COP
kW/kW
3.30
Temp. range of
Indoor
D.B.
15.0~27.0°C (59~81°F)
heating *3 Outdoor
W.B.
-20.0~15.5°C (-4~60°F)
Indoor unit
Total capacity
50~150% of outdoor unit capacity
connectable
Model/Quantity
WP15~WP50/5~50
Sound pressure level (measured in anechoic room) dB <A>
63.5
Sound power level (measured in anechoic room)
dB <A>
87
Refrigerant
High pressure
mm (in.)
22.2 (7/8) Brazed
piping diameter
Low pressure
mm (in.)
28.58 (1-1/8) Brazed
FAN
Type x Quantity
Propeller fan x 2
Air flow rate
m
3
/min
380
L/s
6,333
cfm
13,418
Control, Driving mechanism
Inverter-control, Direct-driven by motor
Motor output
kW
0.92 x 2
*4 External static press.
0 Pa (0 mmH
2
O)
Compressor
Type
Inverter scroll hermetic compressor
Manufacture
AC&R Works, MITSUBISHI ELECTRIC CORPORATION
Starting method
Inverter
Motor output
kW
13.4
Case heater
kW
-
Lubricant
MEL32
External finish
Pre-coated galvanized steel sheets (+powder coating for -BS type)
<MUNSELL 5Y 8/1 or similar>
External dimension H x W x D
mm
1,710 (1,650 without legs) x 1,750 x 740
in.
67-3/8 (65 without legs) x 68-15/16 x 29-3/16
Protection devices
High pressure protection
High pressure sensor, High pressure switch at 4.15 MPa (601 psi)
Inverter circuit (COMP./FAN)
Over-heat protection, Over-current protection
Compressor
-
Fan motor
-
Refrigerant
Type x original charge
R410A x 11.8 kg (27 lbs)
Control
HBC controller
Net weight
kg (lbs)
321 (708)
Heat exchanger
Salt-resistant cross fin & copper tube
HIC circuit (HIC: Heat Inter-Changer)
-
Defrosting method
Auto-defrost mode (Reversed refrigerant cycle, Hot gas)
Drawing
External
WKJ94T178
Wiring
WKE94G042
Standard attachment
Document
Installation Manual
Accessory
Refrigerant conn. pipe
Optional parts
Main HBC controller: CMB-WP108,1016V-GA1
Sub HBC controller: CMB-WP108,1016V-GB1
Remarks
Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be referred
to the Installation Manual.
Due to continuing improvement, above specifications may be subject to change without notice.
Notes:
Unit converter
1.Nominal cooling conditions (subject to JIS B8615-2)
Indoor: 27°CD.B./19°CW.B. (81°FD.B./66°FW.B.), Outdoor: 35°CD.B./24°CW.B. (95°FD.B./75°FW.B.)
Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
2.Nominal heating conditions (subject to JIS B8615-2)
Indoor: 20°CD.B. (68°FD.B.), Outdoor: 7°CD.B./6°CW.B. (45°FD.B./43°FW.B.)
Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
3.-5°CD.B. (23°FD.B.)/-6°CW.B. (21°FW.B.) to 21°CD.B. (70°FD.B.)/15.5°CW.B. (60°FW.B.)
with cooling/heating mixed operation.
4.External static pressure option is available (30 Pa, 60 Pa/3.1 mmH
2
O, 6.1 mmH
2
O).
BTU/h
=kW x 3,412
cfm
=m
3
/min x 35.31
lbs
=kg/0.4536
*Above specification data is
subject to rounding variation.
0000003904.BOOK 8 ページ 2016年1月25日 月曜日 午後2時31分
Summary of Contents for PLFY-WP VBM-E
Page 3: ...MEE15K052 ...
Page 5: ...1 2 MEE15K052 ...
Page 39: ...1 36 MEE15K052 ...
Page 63: ...1 60 MEE15K052 ...
Page 79: ...1 76 MEE15K052 ...
Page 89: ...1 86 MEE15K052 ...
Page 91: ...2 2 MEE15K052 ...
Page 125: ...2 36 MEE15K052 ...
Page 155: ...3 2 MEE15K052 ...
Page 169: ...3 16 MEE15K052 ...
Page 183: ...3 30 MEE15K052 ...