6.2
Installation Environment and Installation Position
6.2.1
Installation environment
(1) Installation location
Do not install the D/A converter module in places where:
• Ambient temperature is outside the range of 0 to 55
;
• Ambient humidity is outside the range of 5 to 95% RH;
• Condensation occurs due to rapid temperature change;
• Corrosive gas or combustible gas is present;
• There are a high level of conductive powder such as dust and iron powder, oil mist, salinity, or organic
solvent;
• It is exposed to direct sunlight;
• A strong electric field or strong magnetic field is generated; and
• The module is subject to vibration and shock.
(2) Installation surface
Install the D/A converter module on a flat surface. Unevenness on the installation surface causes application of
an excessive force to the printed-circuit board, which may lead to a malfunction.
6.2.2
Installation position
When installing the D/A converter module in a control panel, provide a clearance of at least 60mm from the
surroundings including adjacent structures and modules to ensure good ventilation and easy module change.
60mm
or longer
60mm
or longer
60mm
or longer
60mm
or longer
60mm
or longer
60mm
or longer
60mm
or longer