(8) Response time
The following describes the response time until Trigger output completed flag (RX19, RX29) turns on after the
trigger output is requested.
(a) When Trigger output request (RY19) of the main D/A converter module is assigned
to Remote input (RX) using the external signal assignment function
(Response time of the main D/A converter module)
*1
+ (Response time of the extension input module)
*2
[ms]
*1
The response time of the main D/A converter module is calculated as shown below.
(Number of conversion enabled channels in the main D/A converter module)
0.1 [ms]
*2
The response time of the extension input module is the minimum time period until the main D/A converter module
recognizes an input from the extension input module. The response time of the extension input module is calculated as
shown below.
(Input response time setting) + 0.5 [ms]
(b) When Trigger output request (RY19, RY29) is not assigned to Remote input (RX)
using the external signal assignment function
SM
*1
+ LS
*2
+ (Response time of the D/A converter module)
*3
[ms]
*1
SM: Sequence scan time [ms] (
User's manual for the CPU module used in the master station)
*2
LS: Link scan time [ms] (
User's manual for the master/local module used)
*3
The response time of the D/A converter module is calculated as shown below.
Extension analog module
Response time of the D/A converter module
Not connected
Response time of the main D/A converter module:
Number of D/A-conversion enabled channels in the main D/A converter module
0.1 [ms]
Connected
Response time of the main D/A converter module:
Number of D/A-conversion enabled channels in the main D/A converter module
0.2 [ms]
Response time of the extension D/A converter module:
Number of D/A-conversion enabled channels in the extension D/A converter module
0.2 [ms]