140
(4) Devices used by user
Device
Description
X20
Main D/A converter module Digital value write command
QX10 (X20 to X2F)
X22
Main D/A converter module Batch analog output enable command
X24
Main D/A converter module Alert output clear command
X26
Error clear command
X2A
Extension D/A converter module Digital value write command
X2C
Main D/A converter module Batch analog output enable command
X2E
Main D/A converter module Alert output clear command
X1007
Warning flag
NZ2GF2BN-60DA4 (X1000 to X101F)
X1009
Initial data setting completed flag
X100A
Error flag
X100B
Remote READY
X101E
Main D/A converter module Alert output signal
X102E
Extension D/A converter module Alert output signal
NZ2EX2B-60DA4 (X1020 to X102F)
X102F
External power supply READY flag
Y100A
Error clear request flag
NZ2GF2BN-60DA4 (Y1000 to Y101F)
Y1010
Main D/A converter module CH1 Output enable/disable flag
Y1011
Main D/A converter module CH2 Output enable/disable flag
Y101E
Main D/A converter module Alert output clear request flag
Y1020
Extension D/A converter module CH1 Output enable/disable flag
NZ2EX2B-60DA4 (Y1020 to Y102F)
Y1021
Extension D/A converter module CH2 Output enable/disable flag
Y1022
Extension D/A converter module CH3 Output enable/disable flag
Y1023
Extension D/A converter module CH4 Output enable/disable flag
Y102E
Extension D/A converter module Alert output clear request flag
W1002
Main D/A converter module CH1 Digital value
Remote register RWw
W1003
Main D/A converter module CH2 Digital value
W1012
Extension D/A converter module CH1 Digital value
W1013
Extension D/A converter module CH2 Digital value
W1014
Extension D/A converter module CH3 Digital value
W1015
Extension D/A converter module CH4 Digital value
W1100
Latest error code
Remote register RWr
W1101
Latest warning code
W1102
Main D/A converter module CH1 Set value check code
W1103
Main D/A converter module CH2 Set value check code
W110A
Main D/A converter module Alert output flag
W1112
Extension D/A converter module CH1 Set value check code
W1113
Extension D/A converter module CH2 Set value check code
W1114
Extension D/A converter module CH3 Set value check code
W1115
Extension D/A converter module CH4 Set value check code
W111A
Extension D/A converter module Alert output flag