(2) External signal assignment function
This function allows remote input or output signals of the main D/A converter module to be assigned to remote
I/O signals of the extension I/O module connected. Signals can be input from the extension I/O module and error
signals can be output to the external at the fixed timing without influence from the sequence scan or link scan.
(a) How the external signal assignment function operates
Ex.
Assigning Alert output signal (RX1E) of a main D/A converter module to RY2A of an extension output
module
Assigning a remote input signal of the main D/A converter module to a remote output signal of the extension output module
does not allow the assigned remote output signal to be turned on/off or monitored by program. Turn on/off or monitor the pre-
assigned remote input signal of the main module. (In the above example, turn on/off or monitor RY2A.)
Target remote I/O signals of external signal assignment
Area to be set
Trigger output request (RY19)
"Trigger output signal assignment"
Alert output signal (RX1E)
"Alert output signal assignment"
Error flag (RXA)
"Error flag assignment"
Warning flag (RX7)
"Warning flag assignment"
Main D/A converter module
Extension output module
Direction of data flow
The lamp (external device) connected to
the extension output module turns on.
RX1E
RY2A
Alert output
signal
Lamp
(external device)
Controlled by the D/A converter module
Alert output signal (RX1E)
Controlled by means of
the external signal assignment
function
RY2A
(extension output module)
lamp (external device)
Lights out
Lights up
Lights out
OFF
ON
OFF
OFF
ON
OFF