136
CHAPTER 9
PROGRAMMING
This chapter describes the programming of the D/A converter module.
9.1
Precautions for Programming
This section describes precautions when creating the program of CC-Link IE Field Network.
(1) Program for cyclic transmission
For a program for cyclic transmission, provide interlock between the following link special relay (SB) and the link
special register (SW).
• Data link status of the own station (or master station) (SB0049)
• Data link status of each station (SW00B0 to SW00B7)
For the link special relay (SB) and link special register (SW), refer to the following:
User's manual for the master/local module used
Ex.
Interlock example
(2) Program for transient transmission
For a program for transient transmission, provide interlock between the following link special relay (SB) and the
link special register (SW).
• Baton pass status of the own station (or master station) (SB0047)
• Baton pass status of each station (SW00A0 to SW00A7)
For the link special relay (SB) and link special register (SW), refer to the following:
User's manual for the master/local module used
Ex.
Interlock example
Communication program with station No.1
Communication program with station No.2
Dedicated instruction to station No.1
Start-up
contact