196
(15)CH
Scaling lower limit value, CH
Scaling upper limit value
Set the range of scale conversion for each channel.
For details on the scaling function, refer to the following:
• Scaling Function (
(a) Setting range
• Setting range: -32000 to 32000
(b) Enabling the setting
Turn on and off Initial data setting request flag (RY9) to enable the setting.
(c) Default value
The default value is 0 for all channels.
(d) Remote buffer memory address
The remote buffer memory addresses of this area are as follows:
●
A channel where a value out of the range above is set causes an error with the error code (090
H or 190
H) being
stored in Latest error code (RWr0), Error flag (RXA) turning on, and the ERR. LED lighting up.
●
By default, 0 is set and so change the setting value when using the scaling function.
●
The settings must satisfy the condition: Scaling upper limit value > Scaling lower limit value. A channel that does not
satisfy the condition causes an error with the error code (091
H or 191
H) being stored in Latest error code (RWr0),
Error flag (RXA) turning on, and the ERR. LED lighting up.
●
If Scaling enable/disable setting (address: 010EH, 020EH) is set to Disabled (1), the settings of CH
Scaling lower limit
value and CH
Scaling upper limit value are ignored.
(16)Extension module identification code
The identification code of a connected extension module is stored.
If the extension D/A converter module is connected, 2211H is stored.
For the identification codes of extension modules other than the extension D/A converter module, refer to the
following:
Manual including the description of the extension module used
(a) Remote buffer memory address
The remote buffer memory address of this area is as follows:
Remote buffer memory name
Main D/A converter module
Extension D/A converter module
CH1
CH2
CH3
CH4
CH1
CH2
CH3
CH4
CH
Scaling lower limit value
010FH
0111H
0113H
0115H
020FH
0211H
0213H
0215H
CH
Scaling upper limit value
0110H
0112H
0114H
0116H
0210H
0212H
0214H
0216H
Remote buffer memory name
Main D/A converter module
Extension D/A converter module
Extension module identification code
0700H