56
Check the outdoor fan motor.
(Refer to 10-5. .)
Is the fuse (F901) blown on the in-
verter P.C. board?
Check the connection of the connectors
(CN931, CN932) of the outdoor fan motor.
If the connection is poor, make it correct.
Operate the outdoor unit by starting
EMERGENCY OPERATION.
Check the LED indication on the in-
verter P.C. board.
Does the LED blink 10 times?
Replace the inverter P.C. board.
Check the corresponding parts
following LED indication.
(Refer to 10-3.)
Yes
No
Yes
(10-time blink)
No
L Check of inverter P.C. board
OBH733G
Summary of Contents for MUY-GL09NA-U1
Page 9: ...9 5 WIRING DIAGRAM MUZ GL09NA U1 U8 MUZ GL12NA U1 MUZ GL09NA U2 MUZ GL12NA U2 OBH733G ...
Page 10: ...10 MUZ GL09NAH U2 MUZ GL12NAH U2 MUZ GL09NAH U1 U8 MUZ GL12NAH U1 OBH733G ...
Page 11: ...11 MUY GL09NA U1 MUY GL12NA U1 MUY GL09NA U2 MUY GL12NA U2 OBH733G ...
Page 12: ...12 MUZ GL15NA U2 MUZ GL15NA U1 OBH733G ...
Page 13: ...13 MUZ GL15NAH U2 MUZ GL15NAH U1 OBH733G ...
Page 14: ...14 MUY GL15NA U1 MUY GL15NA U2 OBH733G ...
Page 15: ...15 MUZ GL18NA OBH733G ...
Page 16: ...16 MUZ GL18NAH OBH733G ...
Page 17: ...17 MUY GL18NA OBH733G ...
Page 18: ...18 MUZ GL24NA OBH733G ...
Page 19: ...19 MUZ GL24NAH OBH733G ...
Page 20: ...20 MUY GL24NA OBH733G ...
Page 75: ...75 OBH733G ...