42
Outline of the function
This air conditioner can memorize the abnormal condition which has occurred once.
Even though LED indication listed on the troubleshooting check table (10-3.) disappears, the memorized failure details can be recalled.
10-2. FAILURE MODE RECALL FUNCTION
1. Flow chart of failure mode recall function
for the indoor/outdoor unit
NOTE:
1. Make sure to release the failure mode recall function after it is set up, otherwise the unit cannot operate properly.
2. If the abnormal condition is not deleted from the memory, the last abnormal condition is kept memorized.
Does the upper lamp of the OPERATION INDICATOR lamp on
the indoor unit blink at the interval of 0.5 seconds?
Blinks: Either indoor or outdoor unit is abnormal. Beep is
emitted at the same timing as the blinking of the upper
lamp of the OPERATION INDICATOR lamp. 2
Indoor unit is normal.
But the outdoor unit might be abnormal because there are some abnor-
malities that cannot be recalled with this way.
Check if outdoor unit is abnormal according to the detailed outdoor unit
failure mode recall function. (Refer to 10-2.2)
No
Yes
The cause of abnormality cannot be found because the abnormality does not recur.
Setting up the failure mode recall function
Turn ON the power supply.
<Preparation of the remote controller>
While pressing OPERATION SELECT button and TOO COOL button on the remote
controller at the same time, press RESET button.
First, release RESET button.
Hold down the other 2 buttons for another 3 seconds. Make sure that the indicators on
the LCD screen shown in the right figure are all displayed. Then release the buttons.
Press STOP/OPERATE (OFF/ON) button of the remote controller (the set temperature
is displayed) with the remote controller headed towards the indoor unit. 1
Judgment of indoor/outdoor abnormality
Before blinking, does the upper lamp of the OPERATION
INDICATOR lamp stay ON for 3 seconds?
When it stays ON for 3 seconds (without beep): The outdoor unit
is abnormal.
The indoor unit is abnormal.
Check the blinking pattern, and identify the abnormal point by referring to the
indoor unit failure recall mode table. (Refer to indoor unit service manual.)
Make sure to check at least 2 consecutive blinking cycles. 2
Releasing the failure mode recall function
Release the failure mode recall function by the following procedures.
Turn OFF the power supply and turn it ON again.
Press RESET button of the remote controller.
The outdoor unit is abnormal.
Check the blinking pattern, and identify the abnormal point by referring
to the outdoor unit failure recall mode table. (Refer to 10-2.3)
Make sure to check at least 2 consecutive blinking cycles. 3
Repair the failure parts.
Deleting the memorized abnormal condition
After repairing the unit, recall the failure mode again according to "Setting up the failure mode recall
function" mentioned above.
Press STOP/OPERATE (OFF/ON) button of the remote controller (the set temperature is displayed)
with the remote controller headed towards the indoor unit.
Press EMERGENCY OPERATION switch so that the memorized abnormal condition is deleted.
Release the failure mode recall function according to "Releasing the failure mode recall function"
mentioned above.
Operational procedure
Yes
(Blinks)
No
(OFF)
1. Regardless of normal or abnormal condition,
a short beep is emitted once the signal is
received.
2. Blinking pattern when the indoor unit is abnormal:
3.Blinking pattern when the outdoor unit is abnormal:
ON
OFF
Beeps
Repeated cycle
Repeated cycle
ON
OFF
No beep
Beeps
Repeated cycle
2.5-second OFF
Blinking at 0.5-
second interval
2.5-second OFF
3-second ON
Blinking at 0.5-
second interval
Beeps
Repeated cycle
2.5-second OFF
Blinking at 0.5-
second interval
No beep
Beeps
Repeated cycle
2.5-second OFF
3-second ON
Blinking at 0.5-
second interval
Repeated cycle
Beeps
E.g.: MSZ type
MSZ-GL18NA
MSY-GL18NA
MSZ-GL24NA
MSY-GL24NA
MSZ-GL06/09/12/15NA
MSY-GL09/12/15NA
OBH733G
Summary of Contents for MUY-GL09NA-U1
Page 9: ...9 5 WIRING DIAGRAM MUZ GL09NA U1 U8 MUZ GL12NA U1 MUZ GL09NA U2 MUZ GL12NA U2 OBH733G ...
Page 10: ...10 MUZ GL09NAH U2 MUZ GL12NAH U2 MUZ GL09NAH U1 U8 MUZ GL12NAH U1 OBH733G ...
Page 11: ...11 MUY GL09NA U1 MUY GL12NA U1 MUY GL09NA U2 MUY GL12NA U2 OBH733G ...
Page 12: ...12 MUZ GL15NA U2 MUZ GL15NA U1 OBH733G ...
Page 13: ...13 MUZ GL15NAH U2 MUZ GL15NAH U1 OBH733G ...
Page 14: ...14 MUY GL15NA U1 MUY GL15NA U2 OBH733G ...
Page 15: ...15 MUZ GL18NA OBH733G ...
Page 16: ...16 MUZ GL18NAH OBH733G ...
Page 17: ...17 MUY GL18NA OBH733G ...
Page 18: ...18 MUZ GL24NA OBH733G ...
Page 19: ...19 MUZ GL24NAH OBH733G ...
Page 20: ...20 MUY GL24NA OBH733G ...
Page 75: ...75 OBH733G ...