40
SERVICE FUNCTIONS
9
9-1. CHANGE IN DEFROST SETTING (MUZ)
Changing defrost finish temperature
<JS> To change the defrost finish temperature, cut/solder the JS wire of the outdoor inverter P.C. board (Refer to 10-6.1.).
Jumper
Defrost finish temperature
MUZ-GL09/12/15NA
MUZ-GL09/12/15NAH
MUZ-GL18/24NA
MUZ-GL18/24NAH
JS
Soldered
(Initial setting)
41°F (5°C)
50°F (10°C)
None
(Cut)
50°F (10°C)
64°F (18°C)
9-2. PRE-HEAT CONTROL SETTING (MUZ)
MUZ-GL09/12/15/18
When moisture gets into the refrigerant cycle, it may interfere with the startup of the compressor at low outside tempera-
ture. The pre-heat control prevents this interference. The pre-heat control turns ON when the discharge temperature ther-
mistor is 68°F (20°C) or below. When the pre-heat control turns ON, the compressor is energized. (About 50 W)
MUZ-GL24
Prolonged low load operation, in which the thermostat is OFF for a long time, at low outside temperature [32°F (0°C) or
less] may cause the following troubles. The pre-heat control prevents those troubles.
1) If moisture gets into the refrigerant cycle and freezes, it may interfere the startup of the compressor.
2) If liquid refrigerant collects in the compressor, a failure in the compressor may occur.
The pre-heat control turns ON when the compressor temperature is 68°F (20°C) or below. When the pre-heat control
turns ON, the compressor is energized. (About 70 W)
Pre-heat control setting
<JK>
ON: To activate the pre-heat control, cut JK wire of the inverter P.C. board.
OFF: To deactivate the pre-heat control, solder JK wire of the inverter P.C. board.
(Refer to 10-6.1)
Jumper
Pre-heat control setting
MUZ-GL09/12/15/18NA
MUZ-GL09/12/15/18NAH
MUZ-GL24NA
MUZ-GL24NAH
JK
Soldered
Deactivated
(Initial setting)
Deactivated
Cut
Activated
Activated
(Initial setting)
NOTE:
When the inverter P.C. board is replaced, check the JK wire, and cut/solder them if necessary.
MUZ-GL09NA MUZ-GL09NAH MUY-GL09NA
MUZ-GL12NA MUZ-GL12NAH MUY-GL12NA
MUZ-GL15NA MUZ-GL15NAH MUY-GL15NA
MUZ-GL18NA MUZ-GL18NAH MUY-GL18NA
MUZ-GL24NA MUZ-GL24NAH MUY-GL24NA
OBH733G
Summary of Contents for MUY-GL09NA-U1
Page 9: ...9 5 WIRING DIAGRAM MUZ GL09NA U1 U8 MUZ GL12NA U1 MUZ GL09NA U2 MUZ GL12NA U2 OBH733G ...
Page 10: ...10 MUZ GL09NAH U2 MUZ GL12NAH U2 MUZ GL09NAH U1 U8 MUZ GL12NAH U1 OBH733G ...
Page 11: ...11 MUY GL09NA U1 MUY GL12NA U1 MUY GL09NA U2 MUY GL12NA U2 OBH733G ...
Page 12: ...12 MUZ GL15NA U2 MUZ GL15NA U1 OBH733G ...
Page 13: ...13 MUZ GL15NAH U2 MUZ GL15NAH U1 OBH733G ...
Page 14: ...14 MUY GL15NA U1 MUY GL15NA U2 OBH733G ...
Page 15: ...15 MUZ GL18NA OBH733G ...
Page 16: ...16 MUZ GL18NAH OBH733G ...
Page 17: ...17 MUY GL18NA OBH733G ...
Page 18: ...18 MUZ GL24NA OBH733G ...
Page 19: ...19 MUZ GL24NAH OBH733G ...
Page 20: ...20 MUY GL24NA OBH733G ...
Page 75: ...75 OBH733G ...