background image

600

600

175

175

950

25

330

370

E

4

2. Installation location 

2.4. Ventilation and service space

2.4.1. Windy location installation

When installing the outdoor unit on a rooftop or other location unprotected from 
the wind, situate the air outlet of the unit so that it is not directly exposed to strong 
winds. Strong wind entering the air outlet may impede the normal airflow and a 
malfunction may result.
The following shows three examples of precautions against strong winds.

1

  Face the air outlet towards the nearest available wall about 50 cm away from the 

wall. (Fig. 2-3)

2

  Install an optional air guide if the unit is installed in a location where strong winds 

from a typhoon, etc. may directly enter the air outlet. (Fig. 2-4)

 

A

   Air outlet guide

3

  Position the unit so that the air outlet blows perpendicularly to the seasonal wind 

direction, if possible. (Fig. 2-5)

 

B

   Wind  direction

Fig. 2-4

   P71-140

Fig. 2-3

D

C

A

B

A

B

Fig. 2-5

Fig. 3-1

   P71-140

2.4.2. When installing a single outdoor unit (Refer to the last page)

Minimum dimensions are as follows, except for Max., meaning Maximum dimen-
sions, indicated.

The figures in parentheses are for P125, P140 models.

Refer to the figures for each case.

1

 Obstacles at rear only (Fig. 2-6)

2

 Obstacles at rear and above only (Fig. 2-7)

3

 Obstacles at rear and sides only (Fig. 2-8)

4

 Obstacles at front only (Fig. 2-9)

 

*   When using an optional air outlet guide, the clearance for P125, P140 models is 500 mm 

or more.

5

 Obstacles at front and rear only (Fig. 2-10)

 

*   When using an optional air outlet guide, the clearance for P125, P140 models is 500 mm 

or more.

6

 Obstacles at rear, sides, and above only (Fig. 2-11)

  •   Do not install the optional air outlet guides for upward airflow.

2.4.3. When installing multiple outdoor units (Refer to the last page)

Leave 10 mm for P71-140 space or more between the units.

1

 Obstacles at rear only (Fig. 2-12)

2

 Obstacles at rear and above only (Fig. 2-13)

  •   No more than three units must be installed side by side. In addition, leave space as shown.
  •   Do not install the optional air outlet guides for upward airflow.

3

 Obstacles at front only (Fig. 2-14)

 

*   When using an optional air outlet guide, the clearance for P125. P140 models is 1000 mm 

or more.

4

 Obstacles at front and rear only (Fig. 2-15)

 

*   When using an optional air outlet guide, the clearance for P125, P140 models is 1000 mm 

or more.

5

 Single parallel unit arrangement (Fig. 2-16)

  *   When using an optional air outlet guide installed for upward airflow, the clearance is 500 

(1000) mm or more.

6

 Multiple parallel unit arrangement (Fig. 2-17)

  *   When using an optional air outlet guide installed for upward airflow, the clearance is 1000 

(1500) mm or more.

7

 Stacked unit arrangement (Fig. 2-18)

  •   The units can be stacked up to two units high.
  •   No more than 2 stacked units must be installed side by side. In addition, leave space as 

shown.

3. Installing the outdoor unit

•   Be sure to install the unit in a sturdy, level surface to prevent rattling noises dur

-

ing peration. (Fig. 3-1)

<Foundation specifications>

Foundation bolt

M10 (3/8")

Thickness of concrete

120 mm

Length of bolt

70 mm

Weight-bearing capacity

320 kg

•   Make sure that the length of the foundation bolt is within 30 mm of the bottom 

surface of the base.

•   Secure the base of the unit firmly with four-M10 foundation bolts in sturdy loca

-

tions. 

Installing the outdoor unit

•   Do not block the vent. If the vent is blocked, operation will be hindered and 

breakdown may result.

•   In addition to the unit base, use the installation holes on the back of the unit to 

attach wires, etc., if necessary to install the unit. Use self-tapping screws (ø5 × 

15 mm or less) and install on site.

 Warning:

•   The unit must be securely installed on a structure that can sustain its 

weight. If the unit is mounted on an unstable structure, it may fall down 
and cause damage or injuries.

•   The unit must be installed according to the instructions in order to mini

-

mize the risk of damage from earthquakes, typhoons, or strong winds. An 

incorrectly installed unit may fall down and cause damage or injuries.

A

  M10 (3/8") bolt

B

 Base

C

  As long as possible.

D

 Vent

E

  Set deep in the ground.

Max. 30 for P71-140

Min. 10

Min. 360

(mm)

01_BG79U892H05_EN.indd   4

4/19/2016   1:16:00 PM

Summary of Contents for Mr. Slim PU-P HA Series

Page 1: ...ioners PU H P HA INSTALLATION MANUAL For safe and correct use read this manual and the indoor unit installation manual thoroughly before installing the air conditioner unit English 01_BG79U892H05_EN indd 1 4 19 2016 1 16 00 PM ...

Page 2: ...efrigerant R410A to charge the refrigerant lines Do not mix it with any other refrigerant and do not allow air to remain in the lines If air is mixed with the refrigerant then it can be the cause of abnormal high pressure in the refrigerant line and may result in an explosion and other hazards The use of any refrigerant other than that specified for the system will cause mechanical failure or syst...

Page 3: ...ng If dust debris or moisture enters the refrigerant lines oil deterioration or compressor breakdown may result Use ester oil ether oil alkylbenzene oil small amount as the refrigeration oil applied to the flared sections If mineral oil is mixed in the refrigeration oil oil deterioration may result Do not use refrigerant other than R410A refrigerant If another refrigerant is used the chlorine will...

Page 4: ...ace as shown Do not install the optional air outlet guides for upward airflow 3 Obstacles at front only Fig 2 14 When using an optional air outlet guide the clearance for P125 P140 models is 1000 mm or more 4 Obstacles at front and rear only Fig 2 15 When using an optional air outlet guide the clearance for P125 P140 models is 1000 mm or more 5 Single parallel unit arrangement Fig 2 16 When using ...

Page 5: ...or parts of the drain pipe should be wrapped with polyethylene foam insulation materials specific gravity of 0 03 thickness of 9 mm or more Apply thin layer of refrigerant oil to pipe and joint seating surface before tighten ing flare nut A Use 2 wrenches to tighten piping connections B Use leak detector or soapy water to check for gas leaks after connections are completed Apply refrigerating mach...

Page 6: ...d pressure little by little 1 Pressurize to 0 5 MPa 5 kgf cm G wait 5 minutes and make sure the pres sure does not decrease 2 Pressurize to 1 5 MPa 15 kgf cm G wait 5 minutes and make sure the pressure does not decrease 3 Pressurize to 4 15 MPa 41 5 kgf cm G and measure the surrounding tem perature and refrigerant pressure 3 If the specified pressure holds for about one day and does not decrease t...

Page 7: ...dditional refrigerant charging amount 31 40 m 41 50 m P71 140 50 m 30 m 0 6 kg 1 2 kg 4 Installing the refrigerant piping 4 7 For twin triple combination Refrigerant piping limitation of length height difference are shown in the figure Fig 4 8 A Indoor unit B Outdoor unit C Multi distribution pipe option D Height difference Indoor unit Outdoor unit Max 30 m E Height difference Indoor unit Indoor u...

Page 8: ...r switch can result in severe damage to internal parts Keep the power switch turned on during the operational season The followings must be checked as well The outdoor unit is not faulty LED1 and LED2 on the control board of the out door unit flash when the outdoor unit is faulty Both the gas and liquid stop valves are completely open A protective sheet covers the surface of the DIP switch panel o...

Page 9: ...opped However even if the unit is stopped and SW1 1 is set to ON less than three minutes after the compressor stops the refrigerant collecting operation cannot be performed Wait until com pressor has been stopped for three minutes and then set SW1 1 to ON again Set the refrigerant address using the DIP switch of the outdoor unit 1 Wiring from the Remote Control This wire is connected to TB5 termin...

Page 10: ...dicated on the SPEC NAME PLATE Sequential number for each unit 00001 99999 Month of manufacture A 1 B 2 C 3 D 4 E 5 F 6 G 7 H 8 J 9 K 10 L 11 M 12 Year of manufacture western calendar 2014 4 2015 5 01_BG79U892H05_EN indd 10 4 19 2016 1 16 01 PM ...

Page 11: ...d under eneansvar at de herunder beskrevne airconditionanlæg og varmepumper til brug i privat boligbyggeri erhvervsområder og inden for let industri intygar härmed att luftkonditioneringarna och värmepumparna som beskrivs nedan för användning i bostäder kommersiella miljöer och lätta industriella miljöer ev ticaret ve hafif sanayi ortamlarında kullanım amaçlı üretilen ve aşağıda açıklanan klima ve...

Page 12: ...rtalingen van het origineel VOORZICHTIG Het lekken van koelvloeistof kan verstikking veroorzaken Zorg voor ventilatie in overeenstemming met EN378 1 Isoleer de leidingen met isolatiemateriaal Direct contact met de onbedekte leidingen kan leiden tot brandwonden of bevriezing Stop nooit batterijen in uw mond om inslikking te voorkomen Het inslikken van batterijen kan verstikking of vergiftiging vero...

Page 13: ... 2000 100 150 1000 1500 500 800 150 1000 1500 400 600 2000 3000 300 500 Fig 2 6 Fig 2 7 Fig 2 8 Fig 2 9 Fig 2 10 Fig 2 11 Fig 2 12 Fig 2 13 Fig 2 14 Fig 2 15 Fig 2 16 Fig 2 17 Fig 2 18 100 200 200 300 100 200 150 250 150 250 1000 1500 300 500 Max 500 100 150 500 1000 UNIT mm P125 P140 01_BG79U892H05_EN indd 13 4 19 2016 1 16 02 PM ...

Page 14: ...he residential commercial and light industrial environment HEAD OFFICE TOKYO BUILDING 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN Please be sure to put the contact address telephone number on this manual before handing it to the customer 01_BG79U892H05_EN indd 14 4 19 2016 1 16 02 PM ...

Reviews: