1. Safety precautions

1.3. Before electric work 

 Caution:

•   Be sure to install circuit breakers. If not installed, electric shock may re

-

sult.

•   For the power lines, use standard cables of sufficient capacity. Otherwise, 

a short circuit, overheating, or fire may result.

•   When installing the power lines, do not apply tension to the cables. If the 

connections are loosened, the cables can snap or break and overheating 

or fire may result.

•   Be sure to ground the unit. Do not connect the ground wire to gas or water 

pipes, lighting rods, or telephone grounding lines. If the unit is not prop-
erly grounded, electric shock may result.

•   Use circuit breakers (ground fault interrupter, isolating switch (+B fuse), 

and molded case circuit breaker) with the specified capacity. If the circuit 

breaker capacity is larger than the specified capacity, breakdown or fire 

may result.

1.4. Before starting the test run

 Caution:

•   Turn on the main power switch more than 12 hours before starting opera

-

tion. Starting operation just after turning on the power switch can severely 

damage the internal parts. Keep the main power switch turned on during 

the operation season.

•   Before starting operation, check that all panels, guards and other protec

-

tive parts are correctly installed. Rotating, hot, or high voltage parts can 
cause injuries.

•   Do not touch any switch with wet hands. Electric shock may result.

•   Do not touch the refrigerant pipes with bare hands during operation. The 

refrigerant pipes are hot or cold depending on the condition of the flowing 

refrigerant. If you touch the pipes, burns or frostbite may result.

•   After stopping operation, be sure to wait at least five minutes before turn

-

ing off the main power switch. Otherwise, water leakage or breakdown may 
result.

Note:
A low knocking sound might be heard from the Fan Section of this unit dur-

ing the test run. This is caused by the torque fluctuating to control the Fan 

revolutions. This is not a defect in the unit.

1.5. Using R410A refrigerant air conditioners

 Caution:

•   Use new refrigerant pipes.

  Note the following if reusing existing pipes that carried R22 refrigerant.

-   Be sure to clean the pipes and make sure that the insides of the pipes are clean.

-   Replace the existing flare nuts and flare the flared sections again.

-   Do not use thin pipes. (Refer to page 5)

•   Use C1220 copper phosphorus, for copper and copper alloy seamless 

pipes, to connect the refrigerant pipes. Make sure the insides of the pipes 
are clean and do not contain any harmful contaminants such as sulfuric 

compounds, oxidants, debris, or dust. Use pipes with the specified thick

-

ness. (Refer to page 5)

•   Store the pipes to be used during installation indoors and keep both ends 

of the pipes sealed until just before brazing. (Leave elbow joints, etc. in 

their packaging.) If dust, debris, or moisture enters the refrigerant lines, oil 
deterioration or compressor breakdown may result.

•   Use ester oil, ether oil, alkylbenzene oil (small amount) as the refrigeration 

oil applied to the flared sections. If mineral oil is mixed in the refrigeration 

oil, oil deterioration may result.

•   Do not use refrigerant other than R410A refrigerant. If another refrigerant 

is used, the chlorine will cause the oil to deteriorate.

•   Use a vacuum pump with a reverse flow check valve.

   If the vacuum pump oil flows backward into the refrigerant lines, refriger

-

ant oil deterioration may result.

•   Use the following tools specifically designed for use with R410A refriger

-

ant. The following tools are necessary to use R410A refrigerant. Contact 

your nearest dealer for any questions.

Tools (for R410A)

Gauge manifold

Flare tool

Charge hose

Size adjustment gauge

Gas leak detector

Vacuum pump adapter

Torque wrench

Electronic refrigerant charging scale

•   Be sure to use the correct tools. If dust, debris, or moisture enters the re

-

frigerant lines, refrigeration oil deterioration may result.

•   Do not use a charging cylinder. If a charging cylinder is used, the compo

-

sition of the refrigerant will change and the efficiency will be lowered.

2. Installation location

Fig. 2-2

   P71-P140

Fig. 2-1

2.1. Refrigerant pipe (Fig. 2-1) 

   Check that the difference between the heights of the indoor and outdoor 

units, the length of refrigerant pipe, and the number of bends in the pipe 
are within the limits shown below.

Models 

A

 Pipe length 
(one way)

B

   Height  difference

C

  Number of bends 

(one way)

P71,100,125,140

Max. 50 m

Max. 30 m

Max. 15

•   Height difference limitations are binding regardless of which unit, indoor or out

-

door, is positioned higher.

 

D

 Indoor unit

 

E

 Outdoor unit

2.2. Choosing the outdoor unit installation location

•   Avoid locations exposed to direct sunlight or other sources of heat.

•   Select a location from which noise emitted by the unit will not inconvenience 

neighbors.

•   Select a location permitting easy wiring and pipe access to the power source 

and indoor unit.

•   Avoid locations where combustible gases may leak, be produced, flow, or accu

-

mulate.

•   Note that water may drain from the unit during operation.

•   Select a level location that can bear the weight and vibration of the unit.

•   Avoid locations where the unit can be covered by snow. In areas where heavy 

snow fall is anticipated, special precautions such as raising the installation loca-
tion or installing a hood on the air intake must be taken to prevent the snow from 

blocking the air intake or blowing directly against it. This can reduce the airflow 

and a malfunction may result.

•   Avoid locations exposed to oil, steam, or sulfuric gas.

•   Use the transportation handles of the outdoor unit to transport the unit. If the unit 

is carried from the bottom, hands or fingers may be pinched.

2.3. Outline dimensions (Outdoor unit) (Fig. 2-2)

The figure in parenthesis is for P125, P140 models.

A

B

E

D

C

(mm)

01_BG79U892H05_EN.indd   3

4/19/2016   1:16:00 PM

Summary of Contents for Mr. Slim PU-P HA Series

Page 1: ...ioners PU H P HA INSTALLATION MANUAL For safe and correct use read this manual and the indoor unit installation manual thoroughly before installing the air conditioner unit English 01_BG79U892H05_EN indd 1 4 19 2016 1 16 00 PM ...

Page 2: ...efrigerant R410A to charge the refrigerant lines Do not mix it with any other refrigerant and do not allow air to remain in the lines If air is mixed with the refrigerant then it can be the cause of abnormal high pressure in the refrigerant line and may result in an explosion and other hazards The use of any refrigerant other than that specified for the system will cause mechanical failure or syst...

Page 3: ...ng If dust debris or moisture enters the refrigerant lines oil deterioration or compressor breakdown may result Use ester oil ether oil alkylbenzene oil small amount as the refrigeration oil applied to the flared sections If mineral oil is mixed in the refrigeration oil oil deterioration may result Do not use refrigerant other than R410A refrigerant If another refrigerant is used the chlorine will...

Page 4: ...ace as shown Do not install the optional air outlet guides for upward airflow 3 Obstacles at front only Fig 2 14 When using an optional air outlet guide the clearance for P125 P140 models is 1000 mm or more 4 Obstacles at front and rear only Fig 2 15 When using an optional air outlet guide the clearance for P125 P140 models is 1000 mm or more 5 Single parallel unit arrangement Fig 2 16 When using ...

Page 5: ...or parts of the drain pipe should be wrapped with polyethylene foam insulation materials specific gravity of 0 03 thickness of 9 mm or more Apply thin layer of refrigerant oil to pipe and joint seating surface before tighten ing flare nut A Use 2 wrenches to tighten piping connections B Use leak detector or soapy water to check for gas leaks after connections are completed Apply refrigerating mach...

Page 6: ...d pressure little by little 1 Pressurize to 0 5 MPa 5 kgf cm G wait 5 minutes and make sure the pres sure does not decrease 2 Pressurize to 1 5 MPa 15 kgf cm G wait 5 minutes and make sure the pressure does not decrease 3 Pressurize to 4 15 MPa 41 5 kgf cm G and measure the surrounding tem perature and refrigerant pressure 3 If the specified pressure holds for about one day and does not decrease t...

Page 7: ...dditional refrigerant charging amount 31 40 m 41 50 m P71 140 50 m 30 m 0 6 kg 1 2 kg 4 Installing the refrigerant piping 4 7 For twin triple combination Refrigerant piping limitation of length height difference are shown in the figure Fig 4 8 A Indoor unit B Outdoor unit C Multi distribution pipe option D Height difference Indoor unit Outdoor unit Max 30 m E Height difference Indoor unit Indoor u...

Page 8: ...r switch can result in severe damage to internal parts Keep the power switch turned on during the operational season The followings must be checked as well The outdoor unit is not faulty LED1 and LED2 on the control board of the out door unit flash when the outdoor unit is faulty Both the gas and liquid stop valves are completely open A protective sheet covers the surface of the DIP switch panel o...

Page 9: ...opped However even if the unit is stopped and SW1 1 is set to ON less than three minutes after the compressor stops the refrigerant collecting operation cannot be performed Wait until com pressor has been stopped for three minutes and then set SW1 1 to ON again Set the refrigerant address using the DIP switch of the outdoor unit 1 Wiring from the Remote Control This wire is connected to TB5 termin...

Page 10: ...dicated on the SPEC NAME PLATE Sequential number for each unit 00001 99999 Month of manufacture A 1 B 2 C 3 D 4 E 5 F 6 G 7 H 8 J 9 K 10 L 11 M 12 Year of manufacture western calendar 2014 4 2015 5 01_BG79U892H05_EN indd 10 4 19 2016 1 16 01 PM ...

Page 11: ...d under eneansvar at de herunder beskrevne airconditionanlæg og varmepumper til brug i privat boligbyggeri erhvervsområder og inden for let industri intygar härmed att luftkonditioneringarna och värmepumparna som beskrivs nedan för användning i bostäder kommersiella miljöer och lätta industriella miljöer ev ticaret ve hafif sanayi ortamlarında kullanım amaçlı üretilen ve aşağıda açıklanan klima ve...

Page 12: ...rtalingen van het origineel VOORZICHTIG Het lekken van koelvloeistof kan verstikking veroorzaken Zorg voor ventilatie in overeenstemming met EN378 1 Isoleer de leidingen met isolatiemateriaal Direct contact met de onbedekte leidingen kan leiden tot brandwonden of bevriezing Stop nooit batterijen in uw mond om inslikking te voorkomen Het inslikken van batterijen kan verstikking of vergiftiging vero...

Page 13: ... 2000 100 150 1000 1500 500 800 150 1000 1500 400 600 2000 3000 300 500 Fig 2 6 Fig 2 7 Fig 2 8 Fig 2 9 Fig 2 10 Fig 2 11 Fig 2 12 Fig 2 13 Fig 2 14 Fig 2 15 Fig 2 16 Fig 2 17 Fig 2 18 100 200 200 300 100 200 150 250 150 250 1000 1500 300 500 Max 500 100 150 500 1000 UNIT mm P125 P140 01_BG79U892H05_EN indd 13 4 19 2016 1 16 02 PM ...

Page 14: ...he residential commercial and light industrial environment HEAD OFFICE TOKYO BUILDING 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN Please be sure to put the contact address telephone number on this manual before handing it to the customer 01_BG79U892H05_EN indd 14 4 19 2016 1 16 02 PM ...

Reviews: