background image

9

7.2. Test run

7.2.1. Using SW4 in outdoor unit

1) PUH Type

SW4-1

ON

Cooling operation

SW4-2

OFF

SW4-1

ON

Heating operation

SW4-2

ON

2) PU Type

SW4-1

ON

Cooling operation

SW4-2

OFF

*  After performing the test run, set SW4-1 to OFF.

•   After power is supplied, a small clicking noise may be heard from the inside of 

the outdoor unit. The electronic expansion valve is opening and closing. The unit 
is not faulty.

•   A few seconds after the compressor starts, a clanging noise may be heard from 

the inside of the outdoor unit. The noise is coming from the check valve due to 
the small difference in pressure in the pipes. The unit is not faulty.

•   A low knocking sound might be heard from the Fan Section of this unit during 

the test run.

  This is caused by the torque fluctuating to control the Fan revolutions. This is not 

a detect in the unit.

The test run operation mode cannot be changed by DIP switch SW4-2 during 

the test run. (To change the test run operation mode during the test run, stop 

the test run by DIP switch SW4-1. After changing the test run operation mode, 

resume the test run by switch SW4-1.)

7.2.2. Using remote controller

Refer to the indoor unit installation manual.

1 2 3 4 5 6

8. Special Functions

Refrigerant collecting (pump down)

Perform the following procedures to collect the refrigerant when moving the indoor
unit or the outdoor unit.

1

  Supply power (circuit breaker).

 

*   When power is supplied, make sure that “CENTRALLY CONTROLLED” is not 

displayed on the remote controller. If “CENTRALLY CONTROLLED” is dis-
played, the refrigerant collecting (pump down) cannot be completed normally.

  *   Start-up of the indoor-outdoor communication takes about 3 minutes after the 

power (circuit breaker) is turned on. Start the pump-down operation 3 to 4 
minutes after the power (circuit breaker) is turned ON.

2

  After the liquid stop valve is closed, set SW1-1 on the control board of the out-

door unit to ON. The compressor (outdoor unit) and ventilators (indoor and out-
door units) start operating and refrigerant collecting operation begins. LED1 and 
LED2 on the control board of the outdoor unit are lit.

  *   Only set SW1-1 to ON if the unit is stopped. However, even if the unit is 

stopped and SW1-1 is set to ON less than three minutes after the compressor 
stops, the refrigerant collecting operation cannot be performed. Wait until com-
pressor has been stopped for three minutes and then set SW1-1 to ON again.

*  Set the refrigerant address using the DIP switch of the outdoor unit.

1

  Wiring from the Remote Control

This wire is connected to TB5 (terminal board for remote controller) of the indoor 
unit (non-polar).

2

 When a Different Refrigerant System Grouping is Used.

Up to 16 refrigerant systems can be controlled as one group using the slim MA re

-

mote controller.

Note:

In single refrigerant system (twin/triple), there is no need of wiring 

2

.

A

  Outdoor unit

B

  Indoor unit

C

  Master remote controller

D

  Subordinate remote controller

E

  Standard 1:1 (Refrigerant address = 00)

F

  Simultaneous twin (Refrigerant address = 01)

G

  Simultaneous triple (Refrigerant address = 02)

E

  SW 1 - 3 ~ 6

F

  SW 1 - 3 ~ 6

G

  SW 1 - 3 ~ 6

3

  Because the unit automatically stops in about two to three minutes when the re-

frigerant collecting operation is completed (LED1 off, LED2 lit), be sure to quickly 
close the gas stop valve. If LED1 is lit and LED2 is off and the outdoor unit is 
stopped, refrigerant collection is not properly performed. Open the liquid stop 
valve completely, and then repeat step 

2

 after three minutes have passed.

  *   If the refrigerant collecting operation has been completed normally (LED1 off, 

LED2 lit), the unit will remain stopped until the power supply is turned off.

4

  Turn off the power supply (circuit breaker).

 

*  Note that when the extension piping is very long with large refrigerant amount, 

it may not be possible to perform a pump-down operation.

Warning:

When pumping down the refrigerant, stop the compressor before disconnect-
ing the refrigerant pipes. The compressor may burst if air etc. get into it.

9. System control (Fig. 9-1)

Fig. 9-1

SW1
Function table

  <SW1>

Function

Operation according to switch setting

ON

OFF

SW1
function 
settings

1 Compulsory 

defrosting

Start

Normal

2 Error history 

clear

Clear

Normal

3
4
5
6

Refrigerant 
system ad-
dress setting

Settings for outdoor unit addresses 
0 to 15

TB1

A

G

F

A

A

E

B

B

B

B

B

B

D

C

TB1

TB1

TB4

TB5

TB4

TB5

TB4

TB4

TB5

TB4

TB4

1

1

2

 ON
 OFF

 ON
 OFF

 ON
 OFF

3    4    5    6

3    4    5    6

3    4    5    6

 ON
 OFF

2

7. Test run

01_BG79U892H05_EN.indd   9

4/19/2016   1:16:01 PM

Summary of Contents for Mr. Slim PU-P HA Series

Page 1: ...ioners PU H P HA INSTALLATION MANUAL For safe and correct use read this manual and the indoor unit installation manual thoroughly before installing the air conditioner unit English 01_BG79U892H05_EN indd 1 4 19 2016 1 16 00 PM ...

Page 2: ...efrigerant R410A to charge the refrigerant lines Do not mix it with any other refrigerant and do not allow air to remain in the lines If air is mixed with the refrigerant then it can be the cause of abnormal high pressure in the refrigerant line and may result in an explosion and other hazards The use of any refrigerant other than that specified for the system will cause mechanical failure or syst...

Page 3: ...ng If dust debris or moisture enters the refrigerant lines oil deterioration or compressor breakdown may result Use ester oil ether oil alkylbenzene oil small amount as the refrigeration oil applied to the flared sections If mineral oil is mixed in the refrigeration oil oil deterioration may result Do not use refrigerant other than R410A refrigerant If another refrigerant is used the chlorine will...

Page 4: ...ace as shown Do not install the optional air outlet guides for upward airflow 3 Obstacles at front only Fig 2 14 When using an optional air outlet guide the clearance for P125 P140 models is 1000 mm or more 4 Obstacles at front and rear only Fig 2 15 When using an optional air outlet guide the clearance for P125 P140 models is 1000 mm or more 5 Single parallel unit arrangement Fig 2 16 When using ...

Page 5: ...or parts of the drain pipe should be wrapped with polyethylene foam insulation materials specific gravity of 0 03 thickness of 9 mm or more Apply thin layer of refrigerant oil to pipe and joint seating surface before tighten ing flare nut A Use 2 wrenches to tighten piping connections B Use leak detector or soapy water to check for gas leaks after connections are completed Apply refrigerating mach...

Page 6: ...d pressure little by little 1 Pressurize to 0 5 MPa 5 kgf cm G wait 5 minutes and make sure the pres sure does not decrease 2 Pressurize to 1 5 MPa 15 kgf cm G wait 5 minutes and make sure the pressure does not decrease 3 Pressurize to 4 15 MPa 41 5 kgf cm G and measure the surrounding tem perature and refrigerant pressure 3 If the specified pressure holds for about one day and does not decrease t...

Page 7: ...dditional refrigerant charging amount 31 40 m 41 50 m P71 140 50 m 30 m 0 6 kg 1 2 kg 4 Installing the refrigerant piping 4 7 For twin triple combination Refrigerant piping limitation of length height difference are shown in the figure Fig 4 8 A Indoor unit B Outdoor unit C Multi distribution pipe option D Height difference Indoor unit Outdoor unit Max 30 m E Height difference Indoor unit Indoor u...

Page 8: ...r switch can result in severe damage to internal parts Keep the power switch turned on during the operational season The followings must be checked as well The outdoor unit is not faulty LED1 and LED2 on the control board of the out door unit flash when the outdoor unit is faulty Both the gas and liquid stop valves are completely open A protective sheet covers the surface of the DIP switch panel o...

Page 9: ...opped However even if the unit is stopped and SW1 1 is set to ON less than three minutes after the compressor stops the refrigerant collecting operation cannot be performed Wait until com pressor has been stopped for three minutes and then set SW1 1 to ON again Set the refrigerant address using the DIP switch of the outdoor unit 1 Wiring from the Remote Control This wire is connected to TB5 termin...

Page 10: ...dicated on the SPEC NAME PLATE Sequential number for each unit 00001 99999 Month of manufacture A 1 B 2 C 3 D 4 E 5 F 6 G 7 H 8 J 9 K 10 L 11 M 12 Year of manufacture western calendar 2014 4 2015 5 01_BG79U892H05_EN indd 10 4 19 2016 1 16 01 PM ...

Page 11: ...d under eneansvar at de herunder beskrevne airconditionanlæg og varmepumper til brug i privat boligbyggeri erhvervsområder og inden for let industri intygar härmed att luftkonditioneringarna och värmepumparna som beskrivs nedan för användning i bostäder kommersiella miljöer och lätta industriella miljöer ev ticaret ve hafif sanayi ortamlarında kullanım amaçlı üretilen ve aşağıda açıklanan klima ve...

Page 12: ...rtalingen van het origineel VOORZICHTIG Het lekken van koelvloeistof kan verstikking veroorzaken Zorg voor ventilatie in overeenstemming met EN378 1 Isoleer de leidingen met isolatiemateriaal Direct contact met de onbedekte leidingen kan leiden tot brandwonden of bevriezing Stop nooit batterijen in uw mond om inslikking te voorkomen Het inslikken van batterijen kan verstikking of vergiftiging vero...

Page 13: ... 2000 100 150 1000 1500 500 800 150 1000 1500 400 600 2000 3000 300 500 Fig 2 6 Fig 2 7 Fig 2 8 Fig 2 9 Fig 2 10 Fig 2 11 Fig 2 12 Fig 2 13 Fig 2 14 Fig 2 15 Fig 2 16 Fig 2 17 Fig 2 18 100 200 200 300 100 200 150 250 150 250 1000 1500 300 500 Max 500 100 150 500 1000 UNIT mm P125 P140 01_BG79U892H05_EN indd 13 4 19 2016 1 16 02 PM ...

Page 14: ...he residential commercial and light industrial environment HEAD OFFICE TOKYO BUILDING 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN Please be sure to put the contact address telephone number on this manual before handing it to the customer 01_BG79U892H05_EN indd 14 4 19 2016 1 16 02 PM ...

Reviews: