1. Safety precautions

  Before installing the unit, make sure you read all the “Safety precautions”. 

  This equipment does not comply with the relevant technical standard 

for the limitation of flicker and this may cause adverse effects on other 

electrical appliances. Please provide an exclusive circuit for the air con-
dotioner and ensure, the max. impedance in this manual. Do not connect 
other appliances to this circuit.

  Please report to or take consent by the supply authority before connec-

tion to the system. 

After installation work has been completed, explain the “Safety Precautions,” use, 
and maintenance of the unit to the customer according to the information in the 
Operation Manual and perform the test run to ensure normal operation. Both the 
Installation Manual and Operation Manual must be given to the user for keeping. 
These manuals must be passed on to subsequent users.

 : Indicates a part which must be grounded.

 Warning:

Carefully read the labels affixed to the main unit.

 Warning:

•   The unit must not be installed by the user. Ask a dealer or an authorized 

technician to install the unit. If the unit is installed incorrectly, water leak-

age, electric shock, or fire may result.

• 

 For installation work, follow the instructions in the Installation Manual and use 

tools and pipe components specifically made for use with R410A refrigerant. 

The R410A refrigerant in the HFC system is pressurized 1.6 times the pressure 

of usual refrigerants. If pipe components not designed for R410A refrigerant are 

used and the unit is not installed correctly, the pipes may burst and cause dam-

age or injuries. In addition, water leakage, electric shock, or fire may result.

•   The unit must be installed according to the instructions in order to mini

-

mize the risk of damage from earthquakes, typhoons, or strong winds. An 

incorrectly installed unit may fall down and cause damage or injuries.

•   The unit must be securely installed on a structure that can sustain its 

weight. If the unit is mounted on an unstable structure, it may fall down 
and cause damage or injuries.

•   If the air conditioner is installed in a small room, measures must be taken 

to prevent the refrigerant concentration in the room from exceeding the 
safety limit in the event of refrigerant leakage. Consult a dealer regarding 
the appropriate measures to prevent the allowable concentration from be-
ing exceeded. Should the refrigerant leak and cause the concentration limit 

to be exceeded, hazards due to lack of oxygen in the room may result.

•   Ventilate the room if refrigerant leaks during operation. If refrigerant comes 

into contact with a flame, poisonous gases will be released.

•   All electric work must be performed by a qualified technician according to 

local regulations and the instructions given in this manual. The units must 
be powered by dedicated power lines and the correct voltage and circuit 

breakers must be used. Power lines with insufficient capacity or incorrect 

electrical work may result in electric shock or fire.

•   Use C1220 copper phosphorus, for copper and copper alloy seamless 

pipes, to connect the refrigerant pipes. If the pipes are not connected cor-
rectly, the unit will not be properly grounded and electric shock may result.

•   Use only specified cables for wiring. The wiring connections must be made 

securely with no tension applied on the terminal connections. Also, never 
splice the cables for wiring (unless otherwise indicated in this document).

  Failure to observe these instructions may result in overheating or a fire.

•   The terminal block cover panel of the outdoor unit must be firmly attached. 

If the cover panel is mounted incorrectly and dust and moisture enter the 

unit, electric shock or fire may result.

•   When installing or relocating, or servicing the air conditioner, use only the 

specified refrigerant (R410A) to charge the refrigerant lines. Do not mix it 

with any other refrigerant and do not allow air to remain in the lines.

 

If air is mixed with the refrigerant, then it can be the cause of abnormal 
high pressure in the refrigerant line, and may result in an explosion and 

other hazards.

 

The use of any refrigerant other than that specified for the system will cause 
mechanical failure or system malfunction or unit breakdown. In the worst 
case, this could lead to a serious impediment to securing product safety.

•   Use only accessories authorized by Mitsubishi Electric and ask a dealer 

or an authorized technician to install them. If accessories are incorrectly 

installed, water leakage, electric shock, or fire may result.

•   

Do not alter the unit. Consult a dealer for repairs. If alterations or repairs are 

not performed correctly, water leakage, electric shock, or fire may result.

•   The user should never attempt to repair the unit or transfer it to another 

location. If the unit is installed incorrectly, water leakage, electric shock, 

or fire may result. If the air conditioner must be repaired or moved, ask a 

dealer or an authorized technician.

•   After installation has been completed, check for refrigerant leaks. If refrig

-

erant leaks into the room and comes into contact with the flame of a heater 

or portable cooking range, poisonous gases will be released.

1.1. Before installation 

 Caution:

•   Do not use the unit in an unusual environment. If the air conditioner is 

installed in areas exposed to steam, volatile oil (including machine oil), or 
sulfuric gas, areas exposed to high salt content such as the seaside, or 
areas where the unit will be covered by snow, the performance can be sig-

nificantly reduced and the internal parts can be damaged.

•   Do not install the unit where combustible gases may leak, be produced, 

flow, or accumulate. If combustible gas accumulates around the unit, fire 

or explosion may result.

•   The outdoor unit produces condensation during the heating operation. 

Make sure to provide drainage around the outdoor unit if such condensa-
tion is likely to cause damage.

 Warning:

Describes precautions that must be observed to prevent danger of injury or 
death to the user.

 Caution:

Describes precautions that must be observed to prevent damage to the unit.

•   When installing the unit in a hospital or communications office, be pre

-

pared for noise and electronic interference. Inverters, home appliances, 
high-frequency medical equipment, and radio communications equipment 
can cause the air conditioner to malfunction or breakdown. The air con-
ditioner may also affect medical equipment, disturbing medical care, and 
communications equipment, harming the screen display quality.

1.2. Before installation (relocation) 

 Caution:

•   Be extremely careful when transporting or installing the units. 2 or more persons 

are needed to handle the unit, as it weighs 20 kg or more. Do not grasp the pack

-

aging bands. Wear protective gloves to remove the unit from the packaging and 

to move it, as you can injure your hands on the fins or the edge of other parts.

•   

Be sure to safely dispose of the packaging materials. Packaging materials, such 
as nails and other metal or wooden parts may cause stabs or other injuries.

•   The base and attachments of the outdoor unit must be periodically 

checked for looseness, cracks or other damage. If such defects are left un-
corrected, the unit may fall down and cause damage or injuries.

•   Do not clean the air conditioner unit with water. Electric shock may result.

•   Tighten all flare nuts to specification using a torque wrench. If tightened 

too much, the flare nut can break after an extended period and refrigerant 

can leak out.

 Caution:

• Do not vent R410A into the atmosphere.

1.  Safety precautions   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
2.  Installation location  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
3.  Installing the outdoor unit  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
4.  Installing the refrigerant piping  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
5.  Drainage piping work   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

6.  Electrical work . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
7.  Test run . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
8.  Special Functions  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
9.  System control (Fig. 9-1) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
10.  Serial number  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

01_BG79U892H05_EN.indd   2

4/19/2016   1:16:00 PM

Summary of Contents for Mr. Slim PU-P HA Series

Page 1: ...ioners PU H P HA INSTALLATION MANUAL For safe and correct use read this manual and the indoor unit installation manual thoroughly before installing the air conditioner unit English 01_BG79U892H05_EN indd 1 4 19 2016 1 16 00 PM ...

Page 2: ...efrigerant R410A to charge the refrigerant lines Do not mix it with any other refrigerant and do not allow air to remain in the lines If air is mixed with the refrigerant then it can be the cause of abnormal high pressure in the refrigerant line and may result in an explosion and other hazards The use of any refrigerant other than that specified for the system will cause mechanical failure or syst...

Page 3: ...ng If dust debris or moisture enters the refrigerant lines oil deterioration or compressor breakdown may result Use ester oil ether oil alkylbenzene oil small amount as the refrigeration oil applied to the flared sections If mineral oil is mixed in the refrigeration oil oil deterioration may result Do not use refrigerant other than R410A refrigerant If another refrigerant is used the chlorine will...

Page 4: ...ace as shown Do not install the optional air outlet guides for upward airflow 3 Obstacles at front only Fig 2 14 When using an optional air outlet guide the clearance for P125 P140 models is 1000 mm or more 4 Obstacles at front and rear only Fig 2 15 When using an optional air outlet guide the clearance for P125 P140 models is 1000 mm or more 5 Single parallel unit arrangement Fig 2 16 When using ...

Page 5: ...or parts of the drain pipe should be wrapped with polyethylene foam insulation materials specific gravity of 0 03 thickness of 9 mm or more Apply thin layer of refrigerant oil to pipe and joint seating surface before tighten ing flare nut A Use 2 wrenches to tighten piping connections B Use leak detector or soapy water to check for gas leaks after connections are completed Apply refrigerating mach...

Page 6: ...d pressure little by little 1 Pressurize to 0 5 MPa 5 kgf cm G wait 5 minutes and make sure the pres sure does not decrease 2 Pressurize to 1 5 MPa 15 kgf cm G wait 5 minutes and make sure the pressure does not decrease 3 Pressurize to 4 15 MPa 41 5 kgf cm G and measure the surrounding tem perature and refrigerant pressure 3 If the specified pressure holds for about one day and does not decrease t...

Page 7: ...dditional refrigerant charging amount 31 40 m 41 50 m P71 140 50 m 30 m 0 6 kg 1 2 kg 4 Installing the refrigerant piping 4 7 For twin triple combination Refrigerant piping limitation of length height difference are shown in the figure Fig 4 8 A Indoor unit B Outdoor unit C Multi distribution pipe option D Height difference Indoor unit Outdoor unit Max 30 m E Height difference Indoor unit Indoor u...

Page 8: ...r switch can result in severe damage to internal parts Keep the power switch turned on during the operational season The followings must be checked as well The outdoor unit is not faulty LED1 and LED2 on the control board of the out door unit flash when the outdoor unit is faulty Both the gas and liquid stop valves are completely open A protective sheet covers the surface of the DIP switch panel o...

Page 9: ...opped However even if the unit is stopped and SW1 1 is set to ON less than three minutes after the compressor stops the refrigerant collecting operation cannot be performed Wait until com pressor has been stopped for three minutes and then set SW1 1 to ON again Set the refrigerant address using the DIP switch of the outdoor unit 1 Wiring from the Remote Control This wire is connected to TB5 termin...

Page 10: ...dicated on the SPEC NAME PLATE Sequential number for each unit 00001 99999 Month of manufacture A 1 B 2 C 3 D 4 E 5 F 6 G 7 H 8 J 9 K 10 L 11 M 12 Year of manufacture western calendar 2014 4 2015 5 01_BG79U892H05_EN indd 10 4 19 2016 1 16 01 PM ...

Page 11: ...d under eneansvar at de herunder beskrevne airconditionanlæg og varmepumper til brug i privat boligbyggeri erhvervsområder og inden for let industri intygar härmed att luftkonditioneringarna och värmepumparna som beskrivs nedan för användning i bostäder kommersiella miljöer och lätta industriella miljöer ev ticaret ve hafif sanayi ortamlarında kullanım amaçlı üretilen ve aşağıda açıklanan klima ve...

Page 12: ...rtalingen van het origineel VOORZICHTIG Het lekken van koelvloeistof kan verstikking veroorzaken Zorg voor ventilatie in overeenstemming met EN378 1 Isoleer de leidingen met isolatiemateriaal Direct contact met de onbedekte leidingen kan leiden tot brandwonden of bevriezing Stop nooit batterijen in uw mond om inslikking te voorkomen Het inslikken van batterijen kan verstikking of vergiftiging vero...

Page 13: ... 2000 100 150 1000 1500 500 800 150 1000 1500 400 600 2000 3000 300 500 Fig 2 6 Fig 2 7 Fig 2 8 Fig 2 9 Fig 2 10 Fig 2 11 Fig 2 12 Fig 2 13 Fig 2 14 Fig 2 15 Fig 2 16 Fig 2 17 Fig 2 18 100 200 200 300 100 200 150 250 150 250 1000 1500 300 500 Max 500 100 150 500 1000 UNIT mm P125 P140 01_BG79U892H05_EN indd 13 4 19 2016 1 16 02 PM ...

Page 14: ...he residential commercial and light industrial environment HEAD OFFICE TOKYO BUILDING 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN Please be sure to put the contact address telephone number on this manual before handing it to the customer 01_BG79U892H05_EN indd 14 4 19 2016 1 16 02 PM ...

Reviews: