background image

90

°

±

0.5

°

øA

R0.4~R0.8

45

°±

2

°

90

°

0.5

°

øA

R0.4~R0.8

45

°±

2

°

5

4. Installing the refrigerant piping

4.1.  Precautions for devices that use R410A refriger

-

ant

•   Refer to page 3 for precautions not included below on using air condition

-

ers with R410A refrigerant.

•   Use ester oil, ether oil, alkylbenzene oil (small amount) as the refrigeration 

oil applied to the flared sections.

•   Use C1220 copper phosphorus, for copper and copper alloy seamless 

pipes, to connect the refrigerant pipes. Use refrigerant pipes with the 

thicknesses specified in the table to the below. Make sure the insides of 

the pipes are clean and do not contain any harmful contaminants such as 
sulfuric compounds, oxidants, debris, or dust.

 Warning:

 When installing or relocating, or servicing the air conditioner, use only the 

specified refrigerant (R410A) to charge the refrigerant lines. Do not mix it with 

any other refrigerant and do not allow air to remain in the lines.
If air is mixed with the refrigerant, then it can be the cause of abnormal high 

pressure in the refrigerant line, and may result in an explosion and other haz

-

ards.

The use of any refrigerant other than that specified for the system will cause 

mechanical failure or system malfunction or unit breakdown. In the worst 
case, this could lead to a serious impediment to securing product safety.

P71-140

Liquid pipe

ø9.52 thickness 0.8 mm

Gas pipe

ø15.88 thickness 1.0 mm

•   Do not use pipes thinner than those specified above.

4.2. Connecting pipes (Fig. 4-1)

•   When commercially available copper pipes are used, wrap liquid and gas pipes 

with commercially available insulation materials (heat-resistant to 100 °C or 
more, thickness of 12 mm or more).

•   Be sure to separate thermal insulation for gas and liquid refrigerant pipes.

•   The indoor parts of the drain pipe should be wrapped with polyethylene foam 

insulation materials (specific gravity of 0.03, thickness of 9 mm or more).

•   Apply thin layer of refrigerant oil to pipe and joint seating surface before tighten

-

ing flare nut. 

A

•   Use 2 wrenches to tighten piping connections. 

B

•   Use leak detector or soapy water to check for gas leaks after connections are 

completed.

•   Apply refrigerating machine oil over the entire flare seat surface. 

C

•   Use the flare nuts for the following pipe size. 

D

P71-140

Gas side

Pipe size (mm)

ø15.88

Liquid side

Pipe size (mm)

ø9.52

•   When bending the pipes, be careful not to break them. Bend radius of 100 mm 

to 150 mm are sufficient.

•   Make sure the pipes do not contact the compressor. Abnormal noise or vibration 

may result.

1

 Pipes must be connected starting from the indoor unit.

 

Flare nuts must be tightened with a torque wrench.

2

  Flare the liquid pipes and gas pipes and apply a thin layer of refrigeration oil (Ap-

plied on site).

•   When usual pipe sealing is used, refer to Table 1 for flaring of R410A refrigerant 

pipes.

  The size adjustment gauge can be used to confirm A measurements.

 Warning:

When installing the unit, securely connect the refrigerant pipes before start-
ing the compressor

.

A

 (Fig. 4-1)

Copper pipe O.D.

(mm)

Flare dimensions

øA dimensions (mm)

ø6.35

8.7 - 9.1

ø9.52

12.8 - 13.2

ø12.7

16.2 - 16.6

ø15.88

19.3 - 19.7

ø19.05

23.6 - 24.0

B

 (Fig. 4-1)

Copper pipe O.D.  

(mm)

Flare nut O.D.  

(mm)

Tightening torque  

(N·m)

ø6.35

17

14 - 18

ø6.35

22

34 - 42

ø9.52

22

34 - 42

ø12.7

26

49 - 61

ø12.7

29

68 - 82

ø15.88

29

68 - 82

ø15.88

36

100 - 120

ø19.05

36

100 - 120

A

  Flare cutting dimensions

B

  Flare nut tightening torque

A

B

C

D

A

 Die

B

  Copper pipe

A

B

Fig. 4-1

Fig. 4-2

A

Table 1 (Fig. 4-2)

Copper pipe O.D. 

(mm)

A (mm)

Flare tool for R410A

Flare tool for R22·R407C

Clutch type

ø6.35 (1/4")

0 - 0.5

1.0 - 1.5

ø9.52 (3/8")

0 - 0.5

1.0 - 1.5

ø12.7 (1/2")

0 - 0.5

1.0 - 1.5

ø15.88 (5/8")

0 - 0.5

1.0 - 1.5

ø19.05 (3/4")

0 - 0.5

1.0 - 1.5

01_BG79U892H05_EN.indd   5

4/19/2016   1:16:00 PM

Summary of Contents for Mr. Slim PU-P HA Series

Page 1: ...ioners PU H P HA INSTALLATION MANUAL For safe and correct use read this manual and the indoor unit installation manual thoroughly before installing the air conditioner unit English 01_BG79U892H05_EN indd 1 4 19 2016 1 16 00 PM ...

Page 2: ...efrigerant R410A to charge the refrigerant lines Do not mix it with any other refrigerant and do not allow air to remain in the lines If air is mixed with the refrigerant then it can be the cause of abnormal high pressure in the refrigerant line and may result in an explosion and other hazards The use of any refrigerant other than that specified for the system will cause mechanical failure or syst...

Page 3: ...ng If dust debris or moisture enters the refrigerant lines oil deterioration or compressor breakdown may result Use ester oil ether oil alkylbenzene oil small amount as the refrigeration oil applied to the flared sections If mineral oil is mixed in the refrigeration oil oil deterioration may result Do not use refrigerant other than R410A refrigerant If another refrigerant is used the chlorine will...

Page 4: ...ace as shown Do not install the optional air outlet guides for upward airflow 3 Obstacles at front only Fig 2 14 When using an optional air outlet guide the clearance for P125 P140 models is 1000 mm or more 4 Obstacles at front and rear only Fig 2 15 When using an optional air outlet guide the clearance for P125 P140 models is 1000 mm or more 5 Single parallel unit arrangement Fig 2 16 When using ...

Page 5: ...or parts of the drain pipe should be wrapped with polyethylene foam insulation materials specific gravity of 0 03 thickness of 9 mm or more Apply thin layer of refrigerant oil to pipe and joint seating surface before tighten ing flare nut A Use 2 wrenches to tighten piping connections B Use leak detector or soapy water to check for gas leaks after connections are completed Apply refrigerating mach...

Page 6: ...d pressure little by little 1 Pressurize to 0 5 MPa 5 kgf cm G wait 5 minutes and make sure the pres sure does not decrease 2 Pressurize to 1 5 MPa 15 kgf cm G wait 5 minutes and make sure the pressure does not decrease 3 Pressurize to 4 15 MPa 41 5 kgf cm G and measure the surrounding tem perature and refrigerant pressure 3 If the specified pressure holds for about one day and does not decrease t...

Page 7: ...dditional refrigerant charging amount 31 40 m 41 50 m P71 140 50 m 30 m 0 6 kg 1 2 kg 4 Installing the refrigerant piping 4 7 For twin triple combination Refrigerant piping limitation of length height difference are shown in the figure Fig 4 8 A Indoor unit B Outdoor unit C Multi distribution pipe option D Height difference Indoor unit Outdoor unit Max 30 m E Height difference Indoor unit Indoor u...

Page 8: ...r switch can result in severe damage to internal parts Keep the power switch turned on during the operational season The followings must be checked as well The outdoor unit is not faulty LED1 and LED2 on the control board of the out door unit flash when the outdoor unit is faulty Both the gas and liquid stop valves are completely open A protective sheet covers the surface of the DIP switch panel o...

Page 9: ...opped However even if the unit is stopped and SW1 1 is set to ON less than three minutes after the compressor stops the refrigerant collecting operation cannot be performed Wait until com pressor has been stopped for three minutes and then set SW1 1 to ON again Set the refrigerant address using the DIP switch of the outdoor unit 1 Wiring from the Remote Control This wire is connected to TB5 termin...

Page 10: ...dicated on the SPEC NAME PLATE Sequential number for each unit 00001 99999 Month of manufacture A 1 B 2 C 3 D 4 E 5 F 6 G 7 H 8 J 9 K 10 L 11 M 12 Year of manufacture western calendar 2014 4 2015 5 01_BG79U892H05_EN indd 10 4 19 2016 1 16 01 PM ...

Page 11: ...d under eneansvar at de herunder beskrevne airconditionanlæg og varmepumper til brug i privat boligbyggeri erhvervsområder og inden for let industri intygar härmed att luftkonditioneringarna och värmepumparna som beskrivs nedan för användning i bostäder kommersiella miljöer och lätta industriella miljöer ev ticaret ve hafif sanayi ortamlarında kullanım amaçlı üretilen ve aşağıda açıklanan klima ve...

Page 12: ...rtalingen van het origineel VOORZICHTIG Het lekken van koelvloeistof kan verstikking veroorzaken Zorg voor ventilatie in overeenstemming met EN378 1 Isoleer de leidingen met isolatiemateriaal Direct contact met de onbedekte leidingen kan leiden tot brandwonden of bevriezing Stop nooit batterijen in uw mond om inslikking te voorkomen Het inslikken van batterijen kan verstikking of vergiftiging vero...

Page 13: ... 2000 100 150 1000 1500 500 800 150 1000 1500 400 600 2000 3000 300 500 Fig 2 6 Fig 2 7 Fig 2 8 Fig 2 9 Fig 2 10 Fig 2 11 Fig 2 12 Fig 2 13 Fig 2 14 Fig 2 15 Fig 2 16 Fig 2 17 Fig 2 18 100 200 200 300 100 200 150 250 150 250 1000 1500 300 500 Max 500 100 150 500 1000 UNIT mm P125 P140 01_BG79U892H05_EN indd 13 4 19 2016 1 16 02 PM ...

Page 14: ...he residential commercial and light industrial environment HEAD OFFICE TOKYO BUILDING 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN Please be sure to put the contact address telephone number on this manual before handing it to the customer 01_BG79U892H05_EN indd 14 4 19 2016 1 16 02 PM ...

Reviews: