9
NOTE:
1. Rating conditions (ISO T1)
Cooling Indoor : D.B. 27
(80°F) W.B. 19
(66°F) Outdoor : D.B. 35
(95°F) W.B. 24
(75°F)
Heating Indoor : D.B. 20
(68°F)
Outdoor : D.B. 7
(45°F)
W.B. 6
(43°F)
Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range
Indoor
Outdoor
Cooling
Upper limit D.B. 35°C, W.B. 22.5°C D.B. 46°C
Lower limit D.B. 19°C, W.B. 15°C
D.B. -5°C
+
1
Heating
Upper limit D.B. 28°C
D.B. 21°C, W.B. 15°C
Lower limit D.B. 17°C
D.B. -15°C, W.B. -15°C
4. Above data are based on the indicated voltage.
+
1. If optional air protect guide is installed : D.B.-15
Indoor unit
Single phase 230V 50Hz
V : Single phase 230V 50Hz
Y : 3 phase 400V 50Hz
Outdoor unit
3. Guaranteed voltage
198~264V, 50Hz (V) / 342~457V, 50Hz (Y)
Model name
Indoor unit
PKA-RP100KAL
Outdoor unit
PUHZ-P100VHA3
Cooling
Capacity
Btu/h
32,100
kW
9.4 (4.9-11.2)
Total input
kW
3.12
EER
3.01
Energy label class
B
SHF
0.75
Heating
Capacity
Btu/h
38,200
kW
11.2 (4.5-12.5)
Total input
kW
3.49
COP
3.21
Energy label class
C
Booster heater
kW
-
Power supply
Phase
W
1
Cycle
Hz
50
Voltage
V
230
Breaker size
A
32
Indoor unit
Air flow
CMM
20 - 23 - 26
(Low-Mid-High)
CFM
705 - 810 - 920
External pressure
Pa
0
Sound level
dB(A)
41 - 45 - 49
(Low-Mid-High)
External finish
Munsell 1.0Y 9.2/0.2
Dimension
W : mm
1170
D : mm
295
H : mm
365
W : inch
46-1/16
D : inch
11-5/8
H : inch
14-3/8
Weight
kg
21
lbs
46
Field drain pipe I.D.
mm
16
inch
5/8
Outdoor unit
Air flow
CMM
60
CFM
2,120
Sound level at cooling
dB(A)
50
Sound level at heating
dB(A)
54
External finish
Ivory Munsell 3Y 7.8/1.1
Dimension
W : mm
950
D : mm
330+30
H : mm
943
W : inch
37-3/8
D : inch
13 + 1-3/16
H : inch
37-1/8
Weight
kg
75
lbs
165
Refrigerant pipe size
Gas side O.D.
mm
15.88
inch
5/8
Liquid side O.D.
mm
9.52
inch
3/8
Refrigerant pipe length Height difference
m
Max. 30
Length
m
Max. 50
PKA-RP100KAL
PUHZ-P100YHA
50
400
16
77
169
3
2-3. WALL-MOUNTED TYPE