54
7
CORRECTION FACTORS
Refrigerant piping length (one way)
75m
70m
60m
55m
50m
40m
30m
20m
10m
5m
Outdoor unit
Cooling capacity correction factors
PUHZ-P100VHA3
PUHZ-P100YHA
PUHZ-P125VHA3
PUHZ-P125YHA
PUHZ-P140VHA3
PUHZ-P140YHA
PUHZ-P200YHA3
PUHZ-P250YHA3
Heating capacity correction factors
1.00
1.00
1.00
1.00
1.00
0.985
0.981
0.976
0.985
0.981
0.957
0.946
0.931
0.958
0.946
0.931
0.914
0.893
0.931
0.914
0.908
0.885
0.858
0.908
0.885
0.886
0.858
0.827
0.887
0.858
0.876
0.845
0.813
0.876
0.845
—
—
—
0.865
0.834
—
—
—
0.847
0.812
—
—
—
0.838
0.802
Refrigerant piping length (one way)
75m
70m
60m
55m
50m
40m
30m
20m
10m
5m
Outdoor unit
PUHZ-P100VHA3
PUHZ-P100YHA
PUHZ-P125VHA3
PUHZ-P125YHA
PUHZ-P140VHA3
PUHZ-P140YHA
PUHZ-P200YHA3
PUHZ-P250YHA3
1.00
1.00
1.00
1.00
1.00
0.997
0.997
0.997
0.997
0.997
0.991
0.991
0.991
0.991
0.991
0.985
0.985
0.985
0.985
0.985
0.979
0.979
0.979
0.979
0.979
0.973
0.973
0.973
0.973
0.973
0.970
0.970
0.970
0.970
0.970
—
—
—
0.967
0.967
—
—
—
0.961
0.961
—
—
—
0.958
0.958
PUHZ-P100/125/140VHA3
PUHZ-P100/125/140YHA
PUHZ-P200/250YHA3