4
Model name Indoor unit
PLA-RP100BA
PLA-RP125BA
PLA-RP125BA2
Outdoor unit
PUHZ-P100YHA
PUHZ-P125YHA PUHZ-P125YHA
Cooling
Capacity
Btu/h
32,100
42,000
42,000
kW
9.4 (4.9-11.2)
12.3 (5.5-14.0)
12.3 (5.5-14.0)
Total input
kW
3.12
4.09
4.09
EER
3.01
3.01
3.01
Energy label class
B
B
-
SHF
0.74
0.71
0.71
Heating
Capacity
Btu/h
38,200
47,800
47,800
kW
11.2 (4.5-12.5)
14.0 (5.0-16.0)
14.0 (5.0-16.0)
Total input
kW
3.28
4.11
4.02
COP
3.41
3.41
3.48
Energy label class
B
B
-
Booster heater
kW
-
-
-
Power supply Phase
W
3
Cycle
Hz
50
Voltage
V
400
Breaker size
A
16
Indoor unit
Air flow
CMM
20-23-26-30
22-25-28-31
(Low-Medium2-Medium1-High)
CFM
710-810-920-1060
780-880-990-1090
External pressure
Pa
0
0
Sound level
dB(A)
32-34-37-40
34-36-39-41
22-25-28-31
780-880-990-1090
0
34-36-39-41
(Low-Medium2-Medium1-High)
External finish (Panel)
White Munsell 6.4Y 8.9/0.4
Dimension
W : mm
840 (950)
Unit (Panel)
D : mm
840 (950)
H : mm
298 (35)
W : inch
33-1/16 (37-3/8)
D : inch
33-1/16 (37-3/8)
H : inch
11-3/4 (1-3/8)
Weight
kg
25 (6)
Unit (Panel)
lbs
55 (13)
27 (6)
60 (13)
Field drain pipe O.D.
mm
32
inch
1-1/4
Outdoor unit Air flow
CMM
60
100
CFM
2,120
3,530
Sound level at cooling
dB(A)
50
51
51
Sound level at heating
dB(A)
54
55
55
External finish
Ivory Munsell 3Y 7.8/1.1
Dimension
W : mm
950
D : mm
330+30
H : mm
1350
W : inch
37-3/8
D : inch
13 + 1-3/16
H : inch
53-1/8
Weight
kg
101
lbs
222
Refrigerant
pipe size
Gas side O.D.
mm
15.88
inch
5/8
Liquid side O.D.
mm
9.52
inch
3/8
Refrigerant
pipe length
Height difference
m
Max. 30
Length
m
Max. 50
PLA-RP100BA3
PUHZ-P100YHA
32,100
9.4 (4.9-11.2)
3.12
3.01
-
0.74
38,200
11.2 (4.5-12.5)
3.22
3.48
-
-
20-23-26-30
710-810-920-1060
0
32-34-37-40
50
54
943
37-1/8
77
169
PLA-RP140BA2
PUHZ-P140YHA
46,400
13.6 (5.5-15.0)
5.21
2.61
D
0.71
54,600
16.0 (5.0-18.0)
4.98
3.21
C
-
24-26-29-32
850-920-1020-1130
0
36-39-42-44
27 (6)
60 (13)
52
56
26 (6)
25 (6)
55 (13)
57 (13)
NOTE:
1. Rating conditions (ISO T1)
Cooling Indoor : D.B. 27
(80°F) W.B. 19
(66°F) Outdoor : D.B. 35
(95°F) W.B. 24
(75°F)
Heating Indoor : D.B. 20
(68°F)
Outdoor : D.B. 7
(45°F)
W.B. 6
(43°F)
Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range
Indoor
Outdoor
Cooling
Upper limit D.B. 35°C, W.B. 22.5°C D.B. 46°C
Lower limit D.B. 19°C, W.B. 15°C
D.B. -5°C
+
Heating
Upper limit D.B. 28°C
D.B. 21°C, W.B. 15°C
Lower limit D.B. 17°C
D.B. -15°C, W.B. -15°C
4. Above data are based on the indicated voltage.
Indoor unit
Single phase 230V 50Hz
3 phase 400V 50Hz
Outdoor unit
Indoor unit
198~264V, 50Hz
342~457V, 50Hz
Outdoor unit
3. Guaranteed voltage
If optional air protect guide installed. D.B.-15