6
Model name
Indoor unit
PEAD-RP100JA(L)
PEAD-RP125JA(L)
PEAD-RP140JA(L)
Outdoor unit
PUHZ-P100YHA
PUHZ-P125YHA
PUHZ-P140YHA
Cooling
Capacity
Btu/h
32,100
42,000
46,400
kW
9.4 (4.9-11.2)
12.3 (5.5-14.0)
13.6 (5.5-15.0)
Total input
kW
3.04 (3.02)
4.22 (4.20)
4.52 (4.50)
EER
3.09 (3.11)
2.91 (2.93)
3.01 (3.02)
Energy label class
B
C
B
SHF
0.85
0.85
0.84
Heating
Capacity
Btu/h
38,200
47,800
54,600
kW
11.2 (4.5-12.5)
14.0 (5.0-16.0)
16.0 (5.0-18.0)
Total input
kW
3.10
3.87
4.43
COP
3.61
3.62
3.61
Energy label class
A
A
A
Booster heater
kW
-
-
-
Power supply
Phase
W
3
Cycle
Hz
50
Voltage
V
400
Breaker size
A
16
Indoor unit
Air flow
CMM
(Low-Mid-High)
CFM
External pressure
Pa
35 / 50 / 70 / 100 / 150
Sound level
dB(A)
29 - 34 - 38
33 - 36 - 40
34 - 38 - 43
(Low-Mid-High)
External finish
Galvanized sheets
Dimension
W : mm
250
D : mm
1400
H : mm
732
W : inch
D : inch
H : inch
Weight
kg
lbs
mm
inch
Field drain pipe O.D.
32
1-1/4
Outdoor unit
Air flow
CMM
60
100
CFM
2,120
3,530
Sound level at cooling
dB(A)
50
51
52
Sound level at heating
dB(A)
54
55
56
External finish
Ivory Munsell 3Y 7.8/1.1
Dimension
W : mm
950
D : mm
330(+30)
H : mm
943
1350
W : inch
37-3/8
D : inch
13 + 1-3/16
H : inch
37-1/8
53-1/8
Weight
kg
77
101
lbs
169
222
Refrigerant pipe size
Gas side O.D.
mm
15.88
inch
5/8
Liquid side O.D.
mm
9.52
inch
3/8
Refrigerant pipe length
Height difference
m
Max. 30
Length
m
Max. 50
1600
24 - 29 - 34
29.5 - 35.5 - 42
32 - 39 - 46
847-1024-1201
1042-1253-1483
1130-1377-1624
55-1/8
63
28-7/8
9-7/8
41 (40)
43 (42)
47 (46)
91 (89)
95 (93)
104 (102)
NOTE:
1. Rating conditions (ISO T1)
Cooling Indoor : D.B. 27
(80°F) W.B. 19
(66°F) Outdoor : D.B. 35
(95°F) W.B. 24
(75°F)
Heating Indoor : D.B. 20
(68°F)
Outdoor : D.B. 7
(45°F)
W.B. 6
(43°F)
Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range
Indoor
Outdoor
Cooling
Upper limit D.B. 35°C, W.B. 22.5°C D.B. 46°C
Lower limit D.B. 19°C, W.B. 15°C
D.B. -5°C
+
Heating
Upper limit D.B. 28°C
D.B. 21°C, W.B. 15°C
Lower limit D.B. 17°C
D.B. -15°C, W.B. -15°C
4. Above data are based on the indicated voltage.
Indoor unit
Single phase 230V 50Hz
3 phase 400V 50Hz
Outdoor unit
Indoor unit
198~264V, 50Hz
342~457V, 50Hz
Outdoor unit
3. Guaranteed voltage
+
If optional air protect guide installed. D.B.-15