7. SPECIAL ADJUSTMENT FUNCTIONS
7 - 31
(2) Requirements conditions of SEMI-F47 standard
Table 7.2 shows the permissible time of instantaneous power failure for instantaneous power failure of
SEMI-F47 standard.
Table 7.2 Requirements conditions of SEMI-F47 standard
Instantaneous power
failure voltage
Permissible time of
instantaneous power
failure [s]
Rated voltage × 80%
1
Rated voltage × 70%
0.5
Rated voltage × 50%
0.2
(3) Calculation of tolerance against instantaneous power failure
Table 7.3 shows tolerance against instantaneous power failure when instantaneous power failure
voltage is "rated voltage × 50%" and instantaneous power failure time is 200 ms.
Table 7.3 Tolerance against instantaneous power failure
(instantaneous power failure voltage = rated voltage × 50%,
instantaneous power failure time = 200 ms)
Servo amplifier
Instantaneous maximum
output [W]
Tolerance against
instantaneous
power failure [W]
(voltage drop between lines)
MR-J4-10TM 350
250
MR-J4-20TM 700
420
MR-J4-40TM 1400
630
MR-J4-60TM 2100
410
MR-J4-70TM 2625
1150
MR-J4-100TM 3000
1190
MR-J4-200TM 5400
2040
MR-J4-350TM 10500
2600
MR-J4-500TM 15000
4100
MR-J4-700TM 21000
5900
MR-J4-11KTM 40000
2600
MR-J4-15KTM 50000
3500
MR-J4-22KTM 56000
4300
MR-J4-60TM4 1900
190
MR-J4-100TM4 3500
200
MR-J4-200TM4 5400
350
MR-J4-350TM4 10500
730
MR-J4-500TM4 15000
890
MR-J4-700TM4 21000
1500
MR-J4-11KTM4 40000
2400
MR-J4-15KTM4 50000
3200
MR-J4-22KTM4 56000
4200