30
7.2 Checking the IP address
(1) Open the front cover on the server section, and set the MODE
switch to the "STOP" position.
(2) Set the RESET switch to the "SEL." position.
(3) After the "CF CARD" LED turns off, turn the RESET switch to the
"RES."
(4) After all the LEDs except the "POWER" LED on the power supply
section turn off, return the RESET switch to the central position.
(5) Wait until the product starts up and the IP address is displayed on the
7-segment LED at the front.
IP address display (Example of 192.168.10.1 set to CH1 and 192.168.3.1 set to CH2.)
Hexadecimal: C0
Decimal: 192
Hexadecimal: A8
Decimal: 168
Hexadecimal: 0A
Decimal: 10
Hexadecimal: 01
Decimal: 1
Hexadecimal: C0
Decimal: 192
Hexadecimal: A8
Decimal: 168
Hexadecimal: 03
Decimal: 3
Hexadecimal: 01
Decimal: 1
(6) After you finish checking the IP address, turn the MODE switch to the "RUN" position.
7.3 Time limit synchronization of the demand surveillance section
(1) Press TS (time limit synchronization switch) to synchronize the time limit.
Press the TS switch in synchronization with the switching (on the hour or on the half-hour) of the time limit of the
transaction electricity meter.
*
If the product is located at a distance from the transaction electricity meter:
The time limit can also be synchronized by short-circuiting TA and TB instead of pressing TS (time limit synchronization
switch).
Time limit synchronization can be facilitated by connecting a cable equipped with a push button to the TA and TB
terminals and extending it to near the transaction electricity meter.
DEMAND
Press the switch on the
hour or on the
half-hour of the time of
the electricity meter
under surveillance.
Time limit synchronization can be made easy
and accurate by extending the cable from the
TA and TB terminals to the electricity meter
under surveillance and short-circuiting them
while checking the time.