3 - 11
3. SIGNALS AND WIRING
Device Name
Symbol
Description
I/O Division
Temporary stop/Restart
STP
Short STP-SG during automatic operation to make a temporary stop.
Short STP-SG again to make a restart.
Shorting a forward rotation start (ST1) or reverse rotation start (ST2) during
a temporary stop is ignored.
Switching from automatic mode to manual mode during a temporary stop
clears the remaining moving distance.
During home position return and jog operation, the temporary stop/restart
(STP) input is ignored.
(Refer to Section 4.2.5, (4).)
DI-1
Manual pulse generator
multiplication 1
TP0
Used to select the multiplication factor of the manual pulse generator.
When it is not selected, the parameter No.1 (feeding function selection)
setting is made valid.
(Note) Input signals
TP1
TP2
Manual Pulse Generator Multiplication Factor
0
0
Parameter No.1 setting
0
1
1 time
1
0
10 times
1
1
100 times
Manual pulse generator
multiplication 2
TP1
Note: 0: TP1/TP0-SG open
1: TP1/TP0-SG shorted
2) Output devices
Device Name
Symbol
Description
I/O Division
No assigned function
No function is assigned.
Electromagnetic brake
interlock
MBR
Used to output the interlock signal for electromagnetic brake.
MBR-SG are disconnected at servo-off or alarm occurrence.
DO-1
Position range
POT
POT-SG are connected when the actual current position is within the
parameter-set range.
The output is open when home position return completion is incomplete or the
base circuit is off.
DO-1
Warning
WNG WNG-SG are connected when warning occurs.
Open in normal condition.
DO-1
Battery warning
BWNG BWNG-SG are connected when the open battery cable warning (A. 92) or
battery warning (A. 9F) occurs.
Open in normal condition.
DO-1
Limiting torque
TLC
TLC-SG are connected when the torque generated reaches the value set to the
internal torque limit 1 (parameter No. 28) or analog torque limit (TLA). They
are disconnected when the servo-on (SON) switches off.
DO-1
Temporary stop
PUS
PUS-SG are connected when deceleration to a stop is started by the
temporary stop/restart (STP). PUS-SG is disconnected when operation is
resumed by making the temporary stop/restart (STP)valid again.
DO-1
Downloaded from
Summary of Contents for MELSERVO MR-J2 C Series
Page 11: ...A 10 MEMO Downloaded from ManualsNet com search engine ...
Page 33: ...1 16 1 FUNCTIONS AND CONFIGURATION MEMO Downloaded from ManualsNet com search engine ...
Page 73: ...3 36 3 SIGNALS AND WIRING MEMO Downloaded from ManualsNet com search engine ...
Page 127: ...5 18 5 PARAMETERS MEMO Downloaded from ManualsNet com search engine ...
Page 145: ...6 18 6 SERVO CONFIGURATION SOFTWARE MEMO Downloaded from ManualsNet com search engine ...
Page 155: ...7 10 7 DISPLAY AND OPERATION MEMO Downloaded from ManualsNet com search engine ...
Page 189: ...8 34 8 COMMUNICATION FUNCTIONS MEMO Downloaded from ManualsNet com search engine ...
Page 201: ...10 2 10 INSPECTION MEMO Downloaded from ManualsNet com search engine ...
Page 211: ...11 10 11 TROUBLESHOOTING MEMO Downloaded from ManualsNet com search engine ...
Page 219: ...12 8 12 SPECIFICATIONS MEMO Downloaded from ManualsNet com search engine ...
Page 227: ...13 8 13 CHARACTERISTICS MEMO Downloaded from ManualsNet com search engine ...