7 CiA 402 DRIVE PROFILE
7.3 Statusword/Status DO
7.3
Statusword/Status DO
The Statusword objects and the Status DO x objects notify the master station of the PDS state and other drive states. States
defined by CiA 402 are notified by using [Obj. 6041h], and states defined by Mitsubishi Electric are notified by using [Obj.
2D11h].
Bit definition of Statusword
Index
Sub
Object
Name
Data
Type
Access
Description
6041h
VAR
Statusword
U16
ro
2D11h
VAR
Status DO 1
U16
ro
Object defined by Mitsubishi Electric
2D02h
VAR
Status DO 2
U16
ro
Object defined by Mitsubishi Electric
:
:
:
:
:
:
:
Bit
Symbol
Description
0
RTSO
Ready-to-switch-on
1
SO
Switch-on
2
OE
Operation-enabled
3
F
Fault
4
VE
Voltage-enabled
0: The bus voltage is lower than the specified (RA) level.
1: The bus voltage is equal to or higher than the specified level.
5
QS
Quick stop
0: In a Quick stop
1: Not in a Quick stop (including in the test mode)
6
SOD
Switch on disabled
7
W
Warning
0: No warning has occurred.
1: A warning has occurred.
8
The value at reading is undefined.
9
RM
Remote
0: Not following the Controlword command
1: Operating in accordance with the Controlword command
10
OMS
Operation Mode Specific
The definition differs depending on the setting of [Modes of operation (Obj. 6060h)].
MR-J5 User's Manual (Function)
11
ILA
Internal limit active
0: When the forward rotation stroke end, reverse rotation stroke end, and software position limit have not been reached.
1: When the forward rotation stroke end, reverse rotation stroke end, or software position limit has been reached.
(Enabled in csp, csv, pp, pv, or hm mode)
12
OMS
Operation Mode Specific
The definition changes depending on the setting of [Modes of operation].
MR-J5 User's Manual (Function)
13
14
The value at reading is undefined.
15