AC input modules
DC input modules
Relay output module
Triac output module
Transistor output modules – Sink type
Transistor output modules – Source type
Installation and Wiring
Mounting
Connecting the modules
The procedure for connecting modules is shown with an example of how to
connect the L02CPU with the L61P.
Specifications
LX10
LX28
Number of inputs
16
8
Insulation method
Photocoupler
Rated input voltage
100 to 120 V AC
(+10 %/–15 %),
50/60 Hz (±3 Hz)
(Distortion
5 %)
100 to 240 V AC
(+10 %/–15 %),
50/60 Hz (±3 Hz)
(Distortion
5 %)
Inrush current
200 mA within 1 ms
950 mA within 1 ms
Rated input current
6.8 mA
(100 V AC, 50 Hz)
8.2 mA
(100 V AC, 60 Hz)
6.8 mA
(100 V AC, 50 Hz)
8.2 mA
(100 V AC, 60 Hz)
13.7 mA
(200 V AC, 50 Hz)
16.4 mA
(200 V AC, 60 Hz)
Voltage/current for ON
80 V AC/
5 mA (50/60 Hz)
Voltage/current for OFF
30 V AC/
1.7 mA (50/60 Hz)
Input resistance
14.6 k
:
(50 Hz), 12.2 k
:
(60 Hz)
Response
time
OFF
씮
ON
15 ms
(100 V AC, 50/60 Hz)
15 ms
(100 V AC, 50/60 Hz)
10 ms
(200 V AC, 50/60 Hz)
ON
씮
OFF
20 ms
(100 V AC, 50/60 Hz)
20 ms
(100/200 V AC,
50/60 Hz)
External connections
Removable terminal block
Number of occupied I/O
points
16
Internal current
consumption (5 V DC)
90 mA
80 mA
Weight
0.17 kg
0.15 kg
Specifications
LX40C6
LX41C4
LX42C4
Number of inputs
16
32
64
Type of sensors
Positive/negative common
Insulation method
Photocoupler
Rated input voltage
20.4 to 28.8 V DC (ripple ratio
5%)
Rated input current
6 mA
4 mA
Voltage/current for ON
15 V/
4 mA
19 V/
3 mA
Voltage/current for OFF
8 V/
2 mA
9 V/
1.7 mA
Input resistance
3.8 k
:
5.7 k
:
Response
time
(adjustable)
OFF
씮
ON
1/5/10/20/70 ms or less
(Initial setting: 10ms)
ON
씮
OFF
External connections
Removable
terminal block
40-pin
connector
2x40-pin
connector
Number of occupied I/O
points
16
32
64
Internal current
consumption (5 V DC)
90 mA
100 mA
120 mA
Weight
0.15 kg
0.11 kg
0.12 kg
Specifications
LY10R2
Number of outputs
16
Output type
Relay
Insulation method
Relay
Rated switching
voltage/current
24 V DC, 2 A (resistance load) per output
240 V AC, 2 A (cos
M
= 1) per output
8 A per common
Min. switching load
5 V DC, 1 mA
Max. switching voltage
264 V AC/125 V DC
Maximum switching
frequency
3600 times/hour
Response
time
OFF
씮
ON
10 ms
ON
씮
OFF
12 ms
External connections
Removable terminal block
Number of occupied I/O
points
16
Internal current
consumption (5 V DC)
460 mA
Weight
0.21 kg
Specifications
LY20S6
Number of outputs
16
Output type
Triac
Insulation method
Photocoupler
Rated switching voltage
100 to 240 V AC (+10 %/–15 %),
50/60 Hz (±3 Hz)
(Distortion
5 %)
Max. load voltage
264 V AC
Maximum inrush current
20 A
Max. voltage drop at ON
1.5 V (Load current 0.6 A)
Minimum Load
24 V AC/100 mA
100 V AC/25 mA
240 V AC/25 mA
Leakage current at OFF
1.5 mA (120 V, 60 Hz)
3 mA (240 V, 60 Hz)
Response
time
OFF
씮
ON
0.5 x max. 1 ms
ON
씮
OFF
0.5 x max. 1 ms
(rated load, resistive load)
Surge suppressor
CR absorber
Fuse
—
External connections
Removable terminal block
Number of occupied I/O
points
16
Internal current
consumption (5 V DC)
300 mA
Weight
0.22 kg
Specifications
LY40NT5P
LY41NT1P
LY42NT1P
Number of outputs
16
32
64
Output type
Transistor (sink)
Insulation method
Photocoupler
Rated load voltage
10.2 to 28.8 V DC
Maximum load current
0.5 A per
output
5 A per
common
0.1 A per output
2 A per common
Maximum inrush current
Current is limited by the overload protection
function.
Leakage current at OFF
0.1 mA
Max. voltage drop at ON
0.3 V DC
at 0.5 A
0.2 V DC at 0.1 A
Response
time
OFF
씮
ON
0.5 ms
ON
씮
OFF
1 ms (rated load, resistance load)
Surge suppressor
Zener diode
Fuse
—
External
power
supply
Voltage
10.2 to 28.8 V DC (ripple ratio
5 %)
Current
9 mA
(at 24 V DC)
13 mA
(at 24 V DC)
9 mA
(at 24 V DC)
per common
External connections
Removable
terminal block
40-pin
connector
2x40-pin
connector
Number of occupied I/O
points
16
32
64
Internal current
consumption (5 V DC)
100 mA
140 mA
190 mA
Weight
0.15 kg
0.11 kg
0.12 kg
Specifications
LY40PT5P
LY41NPT1P
LY42PT1P
Number of outputs
16
32
64
Output type
Transistor (source)
Insulation method
Photocoupler
Rated load voltage
10.2 to 28.8 V DC
Maximum load current
0.5 A per
output
5 A per
common
0.1 A per output
2 A per common
Maximum inrush current
Current is limited by the overload
protection function.
Leakage current at OFF
0.1 mA
Max. voltage drop at ON
0.3 V DC
at 0.5 A
0.2 V DC at 0.1 A
Response
time
OFF
씮
ON
0.5 ms
ON
씮
OFF
1 ms (rated load, resistance load)
Surge suppressor
Zener diode
Fuse
—
External
power
supply
Voltage
10.2 to 28.8 V DC (ripple ratio
5%)
Current
17 mA
(at 24 V DC)
20 mA
(at 24 V DC)
20 mA
(at 24 V DC)
per common
External connections
Removable
terminal block
40-pin
connector
2x40-pin
connector
Number of occupied I/O
points
16
32
64
Internal current
consumption (5 V DC)
100 mA
140 mA
190 mA
Weight
0.15 kg
0.11 kg
0.12 kg
P
DANGER
Turn off all phases of the power supply for the PLC and other external
sources before starting the installation or wiring work.
E
CAUTION
●
Use the product in the environment within the general specifications
described in the MELSEC L series CPU Module User's Manual. Never use
the product in areas with dust, oily smoke, conductive dusts, corrosive
or flammable gas, vibrations or impacts, or expose it to high tempera-
ture, condensation, or wind and rain.
●
When drilling screw holes or wiring, cutting chips or wire chips should
not enter ventilation slits. Such an accident may cause fire, failure or
malfunction.
●
A protective film is attached onto the module top to prevent foreign
matter such as wire chips entering the module during wiring. Do not
remove the film during wiring. Remove it for heat dissipation before
system operation.
●
Before handling modules, touch a grounded metal object to discharge
the static electricity from the human body. Not doing so may cause
failure or malfunctions of the module.
E
CAUTION
●
Modules must be mounted on a DIN rail.
●
Connect an END cover on the last module on the right side.
●
Do not drop the module or subject it to heavy impact.
●
Do not open or modify a module. Doing so can cause a failure, malfunction,
injury or fire.
●
Do not touch the conductive parts of the module directly.
●
To interconnect modules, engage the respective connectors and se-
curely lock the module joint levers. Incorrect interconnection may
cause malfunction, failure, or drop of the module.
햲
To release the module joint
levers located at the top and
bottom of the L02CPU:
Slide the levers toward the
front side of the module.
햳
Insert the connector of the
power supply module into
that of the CPU module so
that they are securely engaged.
햴
To lock the module joint levers:
Slide the levers toward the
back side of the module.
Make sure that the modules
are securely connected.
Release