APPENDIX 3 CABLE MANUFACTURING DRAWING
Appendix 3.3 FCUA-R220 Cable Manufacturing Drawing
I
-27
Appendix 3.3 FCUA-R220 Cable Manufacturing Drawing
Application:
Supply of 24V to remote I/O unit (FCU6-DX561)
Option (compatible connector set)
FCUA-CN220
(Note that this corresponds only to the connector on the remote I/O unit side.)
Assembly drawing
R220
Note (3)
F G
+24V
GND
1 2
3
4
R220
Connection diagram
BROWN
WHITE
3
2
1
FG
GND
+24V
FG
GND
+24V
Power supply side
Remote I/O unit (FCU6-DX561) side
DCIN
Manufacturing precautions
(1) The wire material shall be a shielded 1-pair stranded cable equivalent to AWG20 (0.5mm
2
).
(If the cable length exceeds 10m, use AWG16 (1.25mm
2
).)
(2) The parts used shall be Mitsubishi recommended parts. Equivalent parts may be used providing
they are compatible with the specifications.
(3) Attach the nameplate (with protective cover stamped with the cable name) in the position designated
in the assembly drawing.
(4) Install each crimp terminal side after stamping the name of each signal on the mark tube.
(5) Protect both ends of the wire material with insulation bushing.
(6) Use AWG18 (0.75mm
2
) or equivalent for the shield treatment wire material.
List of parts used
No.
Part name/model
Maker
Qty.
1
Connector
2-178288-3
Tyco
Electronics
AMP
1
2
Contact
1-175218-5
Tyco
Electronics
AMP
3
3
Wire material
JPVV-SB
1P × 0.5mm
2
BANDO
Electric Wire
Note (1)
(1)
4
Solderless terminal
V1.25-3
J.S.T. 3
Max. cable length: 30m