3 - 29 3 - 29
MELSEC-Q
3 SPECIFICATIONS
Address
Decimal (Hex)
Application Name
Initial
value
Protocol
Registration
Reference
section
CH1 CH2
MC Non Bi Pd
515
(203
H
)
For confirmation
of switch setting
and mode
switching
Switch setting error and mode switching error status
0: No error
Other than 0: Switch setting error and mode switching error
0 R
Not allowed
Section 4.3
Section 4.5.2
Section 9.6.10
CH1 Communication protocol setting No. (b0)
0: Normal
1: Error
CH1 Communication rate setting (b1)
0: Normal
1: Error
CH1 Setting change prohibit time mode switching (b3)
0: Normal
1: Error
CH2 Communication protocol setting No. (b4)
0: Normal
1: Error
CH2 Communication rate setting (b5)
0: Normal
1: Error
CH2 Setting change prohibit time mode switching (b7)
0: Normal
1: Error
Setting station No. (b14)
0: Normal
1: Error
Linked operation setting (b15)
0: Normal
1: Error
516
(204
H
)
For confirmation
of user frame
Number of registered user frames
D
epe
nd
s
on
r
eg
ist
ra
tion
st
at
us
R —
Not
allowed
Section 9.6.10
0: No registration
1 to 200: Number of registered frames
517 to 541
(205
H
to 21D
H
)
User frame registration status (for confirmation of registration No.)
0: No registration
1: Registered
Bit corresponding to registration No. is 0(OFF)/1(ON).
Registration No.3E8
H
(1000) : Address 205
H
(b0) to
Registration No. 4AF
H
(1199) : Address 211
H
(b7)
542
(21E
H
)
Number of registered default registration frames (for system)
Section 9.6.10
User's Manual
(Application)
543
(21F
H
)
Use prohibited
System area
—
544
(220
H
)
For confirmation
of flash ROM
write result
Flash ROM system parameters write result
0
RW Not
allowed
Section 9.6.10
0
: Normal completion
Other than 1 (error code) : Abnormal completion
545
(221
H
)
For confirmation
of modem
function
Modem function error code (error code when modem function is
being used)
RW
—
Not allowed
Section 9.6.2
User's Manual
(Application)
0
: Normal completion
Other than 1 (error code) : Abnormal completion
R
546
(222
H
)
Modem function sequence status
0: Idle
1: Waiting for initialization
2: Initializing modem
3: Waiting
4: Checking password
5: Communicating
6: Notification in progress
7: Modem disconnected
8: Callback Request reception
waiting
9: Callback Modem disconnect
waiting
10: Callback Delay time waiting
11: Callback Reconnecting
12: Callback Rechecking password
547
(223
H
)
Number of data registration for connection
D
epe
nd
s on
r
eg
ist
ra
tion
st
at
us
0: No registration
1 to 30: Number of registrations
548 to 549
(224
H
to 225
H
)
Data registration status for connection
(for confirmation of registration No.)
0: No registration
1: Registered
Bit corresponding to registration No. is 0(OFF)/1(ON).
Registration No. BB8
H
(3000) : Address 224
H
(b0) to
Registration No. BD5
H
(3029) : Address 225
H
(b13)
550
(226
H
)
Number of data registration for initialization
0: No registration
1 to 30: Number of registrations
Summary of Contents for GX Configurator-SC
Page 2: ......
Page 103: ...3 42 3 42 MELSEC Q 3 SPECIFICATIONS MEMO ...
Page 138: ...4 35 4 35 MELSEC Q 4 SETTINGS AND PROCEDURES PRIOR TO OPERATION MEMO ...
Page 397: ...App 24 App 24 MELSEC Q APPENDICES Connection example 3 Connection example 4 ...
Page 439: ...WARRANTY ...
Page 441: ......