11 TROUBLESHOOTING
Error code
(Hexa-
decimal)
Error
Description
Signal
name
Corrective action
Protocol
MC
Non
Proce-
dure
Bidire-
ctional
Pre-
defined
7F68
H
Framing
error
Data does not match the stop bit
setting.
A malfunction occurred in the network
because the power source of the
partner station was on or off.
Noise occurs in the network.
When the multidrop was connected,
data was transmitted simultaneously by
multiple devices.
SIO
Match the Q series C24 and external
device settings.
Clear the error information according to
the ERR. clear request (YE/YF).
In addition, when communicating data
with the non procedure protocol,
execute the INPUT instruction, and
read and discard the unnecessary data.
Measure the noise.
When connecting the multidrop, remove
the interlock so that data will not be
transmitted simultaneously by multiple
devices.
7F69
H
Parity
error
Data does not match the parity bit
setting.
A malfunction occurred in the network
because the power source of the
partner station was on or off.
Noise occurs in the network.
When the multidrop was connected,
data was transmitted simultaneously by
multiple devices.
P/S
Match the Q series C24 and external
device settings.
Clear the error information according to
the ERR. clear request (YE/YF).
In addition, when communicating data
with the non procedure protocol,
execute the INPUT instruction, and
read and discard the unnecessary data.
Measure the noise.
When connecting the multidrop, remove
the interlock so that data will not be
transmitted simultaneously by multiple
devices.
7F6A
H
Buffer full error
OS receive buffer overflowed and
receive data was skipped.
SIO
Use DTR and DC control and perform
data communications so that the buffer
does not become full. (Perform RS
CS
control when the modem function is
used.)
If the Read Request signal was turned
ON, execute read immediately.
7F6B
H
CD(DCD) signal
control error
Data was received when CD(DCD)
signal is OFF when "CD terminal check
enabled" was designated.
CHn
ERR.
Recheck the CD(DCD) signal control of
the external device.
(Send while the CD(DCD) signal is ON.)
Set "no CD terminal checking" and
perform communication.
7F6C
H
Transmission
error
Data cannot be sent because the line is
not connected.
CHn
ERR.
Transmit data after line connection
processing on the interface side that
uses the modem function.
Summary of Contents for GX Configurator-SC
Page 2: ......
Page 103: ...3 42 3 42 MELSEC Q 3 SPECIFICATIONS MEMO ...
Page 138: ...4 35 4 35 MELSEC Q 4 SETTINGS AND PROCEDURES PRIOR TO OPERATION MEMO ...
Page 397: ...App 24 App 24 MELSEC Q APPENDICES Connection example 3 Connection example 4 ...
Page 439: ...WARRANTY ...
Page 441: ......