3 - 2 3 - 2
MELSEC-Q
3 SPECIFICATIONS
(Continued from preceding page)
Item
Specifications
QJ71C24N
QJ71C24
QJ71C24N-R2
QJ71C24-R2
QJ71C24N-R4
Transmission control
RS-232
RS-422/485
DTR/DSR
control
Enabled
Disabled
RS/CS
control
Enabled
Disabled
CD(DCD) signal control
Enabled
Disabled
DC1/DC3 (Xon/Xoff) control
DC2/DC4 control
Enabled Enabled
DTR/DSR signal control and DC code control are selected by the user.
Line configuration
(Connection) (
2)
RS-232 1:1
1:1
—
RS-422/485
1:1, 1:n, n:1, m:n
—
1:1, 1:n, n:1, m:n
Line configuration
(Data
communication)
(
2)
RS-
232
MC protocols
communication
1:1 1:1
—
Non procedure
protocol
communication
1:1 1:1
Bidirectional
protocols
communication
1:1 1:1
Pre-defined protocol
communication (
6)
1:1 1:1
RS-
422/
485
MC protocols
communication
1:1, 1:n, m:n
—
1:1, 1:n, m:n
Non procedure
protocol
communication
1:1, 1:n, n:1
1:1, 1:n, n:1
Bidirectional
protocols
communication
1:1 1:1
Pre-defined protocol
communication (
6)
1:1, n:1
1:1, n:1
Transmission
distance (Overall
distance)
RS-232
Maximum 15 m
(49.2 ft.)
Maximum 15 m
(49.2 ft.)
—
RS-422/485
Maximum 1200 m (3937 ft.)
(overall distance)
—
Maximum 1200 m (3937 ft.)
(overall distance)
Flash ROM write count
Maximum 100,000 times to the same area
Number of occupied I/O points
32 points per slot (I/O assignment: Intelli: 32 points) (
3)
Recommended
cable
RS-232
7/0. 127 P HRV-SV Outside diameter 8.5mm (0.33in.) or more
(Oki Electric Cable Co., Ltd. Applicable number is specified in .)
RS-422/485
SPEV (SB)-MPC-0.2
3P Outside diameter approx. 6.5mm (0.26 in.) (Mitsubishi Cable Industries,
LTD.)
SPEV(SB)-0.2
3P Outside diameter approx. 7.5mm (0.3 in.) (Mitsubishi Cable Industries, LTD.) (
4)
Applicable connector for external wiring
D-sub 9 pin (male) screw type (
5)
—
5V DC internal current consumption
0.31A
0.26A
0.39A
External dimensions
98 (3.86 in.) (H)
27.4 (1.08 in.) (W)
90 (3.54 in.) (D)[mm]
Weight
0.20kg (0.44lb)
1 Set to transfer data with external devices using a full-duplex communication system when the Q series
C24 is started. For switching to a half-duplex communication system, refer to the User's Manual
(Application).
2 Indicates possible combinations when connecting the programmable controller CPU and external devices
(external device side: programmable controller CPU side). The total number of n and m+n is up to 32
stations.
3 In order to use the Q series C24, it is necessary to set the GX Developer switches.
To set the GX Developer switches, refer to Section 4.5.
4 Recommended cables SPEV (SB)-MPC-0.2
3P and SPEV (SB)-0.2
3P
are
equivalent in the
electrical characteristics, but partially different in the outside diameter, internal wire colors, etc.
5 See Section 3.2.1 (3) for the recommended connector.
6 Pre-defined protocol communication is available for the QJ71C24N, QJ71C24N-R2, and QJ71C24N-R4.
3
Summary of Contents for GX Configurator-SC
Page 2: ......
Page 103: ...3 42 3 42 MELSEC Q 3 SPECIFICATIONS MEMO ...
Page 138: ...4 35 4 35 MELSEC Q 4 SETTINGS AND PROCEDURES PRIOR TO OPERATION MEMO ...
Page 397: ...App 24 App 24 MELSEC Q APPENDICES Connection example 3 Connection example 4 ...
Page 439: ...WARRANTY ...
Page 441: ......