27
Dancer control detail
3.7.2
Dancer roll target position (Pr. 133, Pr. 702, Pr. 731)
(1) Dancer signal input selection
(Pr. 731)
Use
Pr. 731
to assign a terminal for the dancer signal input.
(2) PID set point
(Pr. 133)
Set the desired set point (%) with parameter.
Set the target position of dancer roll (center position) in
Pr. 133
.
If position signal from dancer roll to the terminal 1 is 10V at the upper limit position, -10V at the lower limit position, and 0V
at the center position (target position), set 500% in
Pr. 133
.
If -5V at the center (target position), set 450% to
Pr. 133
.
-10V to 10V of voltage can be input to terminal 1.
Y54 signal is ON when dancer roll, which is viewed from the target position, is within the range set in
Pr. 702
.
(3) Dancer roll position detection
(Pr. 702)
Dancer roll position detection signal Y54 is output when dancer roll, which is viewed from the target position, is within the
range set in
Pr. 702
. Set "54 (positive logic) or 154 (negative logic)" in any of
Pr. 190 to Pr. 196 (Output terminal function
selection)
to assign Y54 signal to an output terminal.
Setting in
Pr.731
Input terminal
3
Terminal 2 (0 to 100%)
4
Terminal 4 (0 to 100%)
5 (Initial value)
Terminal 1 (-100 to 100%)
6
Terminal 6 (-100 to 100%) (FR-A7AZ)
Setting in
Pr.133
Set point
600%
+100%
500%
0%
400%
-100%
REMARKS
• Dancer position can be monitored in % by setting
Pr. 52
= "27".
• The automatic restart after instantaneous power failure function is disabled when the dancer control is valid (
Pr. 128
= "40, 41").
Parameter
Number
Name
Setting Range
Increments
Initial Value
702
Dancer position detection level
0 to 100%
0.1%
10%
Dancer roll position signal
(
Pr. 133
(Target dancer position))
Dancer roll position signal
(
Pr. 133
(Target dancer position))
10V(600%)
10V, 20mA(600%)
7.5V, 16mA(550%)
5V(550%)
Dancer roll lower limit
Dancer roll lower limit
-5V(450%)
-10V(400%)
Dancer roll
upper limit
0(500%)
Center position
Dancer roll
upper limit
Dancer signal terminal 1, terminal 6 input
Dancer signal terminal 2, terminal 4 input
5V, 12mA(500%)
2.5V, 8mA(450%)
0V, 4mA(400%)
Center position
(Target position)
Upper limit
Lower limit
Pr. 702
Pr. 702
Dancer roll detection level
Y54 turns ON when the dancer roll
is within this range.