Profibus PROFILES
30
*1
Description is not included in the ASCII file itself.
*2
Use "Mitsubishi" if the maximum number of characters of the vendor-
name of the master used is 10.
5.2 Slave User Parameter
By changing the slave user parameter value, you can use the byte
swapping function (byte inversion function).
Setting "1" at Address 1H (Bit 0) makes the byte swapping function valid.
Since "-" is an unused bit, set "0".
Ext_User_Prm_Data_
Const(1)
00
H
Initial value of user parameter's second
byte
Ext_User_Prm_Data_
Ref(1)
1
Byte swapping selection 1 is used on text
base in user parameter's second byte.
Module
"
PPO type 1
"
F3
H
, F1
H
PPO type 1 selection
EndModule
Module
"
PPO type 2
"
F3
H
, F5
H
PPO type 2 selection
EndModule
Module
"
PPO type 3
"
F1
H
PPO type 3 selection
EndModule
Module
"
PPO type 4
"
F5
H
PPO type 4 selection
EndModule
Module
"
PPO type 5
"
F3
H
, F9
H
PPO type 5 selection
EndModule
Address
Function
0
H
For manufacturer’s setting (Value should be "1".)
1
H
15
Bit
14
Bit
13
Bit
12
Bit
11
Bit
10
Bit
9
Bit
8
Bit
-
-
-
-
-
-
-
-
7
Bit
6
Bit
5
Bit
4
Bit
3
Bit
2
Bit
1
Bit
0
Bit
-
-
-
-
-
-
-
0:Byte
swapping
invalid
1:Byte
swapping
valid
Parameter
Value
Description*1