BUFFER MEMORY DETAILS
38
PZD
ZSW
-
0 to 2 Not used (1 is returned)
Fault
(Alarm
signal)
3
0:Inverter normal
1:Inverter alarm occurrence
-
4 to 5 Not used (1 is returned)
Power-
on inhibit
6
0 is returned
Alarm
7
0:Command execution normal
1:Command execution error
-
8
Not used (0 is returned)
Control
request
9
1 is returned
FU
signal
10
0:OFF
1:ON (Output frequency being detected)
Refer to Pr. 42 and Pr. 43 in the inverter manual.
RUN
signal
11
0:OFF
1:ON (Inverter running)
FWD
12
0:Other than forward operation being performed
(at a stop, reverse rotation operation being
performed)
1:Forward rotation operation being performed
REW
13
0:Other than reverse operation being performed
(at a stop, forward rotation operation being
performed)
1:Reverse rotation operation being performed
Operation
mode
14
0:Other than network operation mode
1:Network operation mode
BUSY
15
0:Ready status
1:Busy status
If it takes time to perform slave side processing,
slave side busy status is announced since reply to
master will be delayed.
In busy status, other response data are unfixed
values. When slave side is busy, request from
master is invalid. Therefore, the same request must
be sent again. During busy status, 0 is returned for
all Bits except for Bit 15.
HSW
0 to 15 Set frequency (0.01 Hz increments)
HIW
0 to 15 Running frequency (0.01 Hz increments)
FR-A500/F500
series
Name
Bit
Description