INVERTER SETTING
19
3.4 Operation at Communication Error Occurrence
3.4.1 Operation selection at communication error
occurrence (For the FR-A500/V500 series only)
You can select operations at error occurrences by setting Pr. 500 to Pr.
502 under network operation.
• Parameter setting
1) Pr. 500 "communication error recognition waiting time"
You can set the waiting time from when a communication line fault
occurs until it is recognized as a communication error.
If the communication line fault still persists after the time set in Pr. 500
has elapsed, it is recognized as a communication error.
When the fault is restored to normal communication within the set time,
it is not regarded as a communication error and operation continues.
REMARKS
For the FR-A500, Pr. 500 to Pr. 502 are available with an upgraded inverter.
Refer to the inverter manual for the availability of the parameters.
Parameter Number Setting Range
Minimum Setting
Increments
Factory Setting
500
0 to 999.8s
0.1s
0
Recognition
Normal
Abnormal
Time set in Pr. 500
Communication line status
Communication error (E. OP3)