3. Name and function of each part
・
Name of each part
Contact/ pulse input terminals
Contact/ pulse output terminals
Frame GND terminal
Power supply terminals
Voltage input terminals
LCD
display
Operation
button
Communication terminals (MODBUS
®
RTU)
Current input terminals
・
Back view
IEC rail fixture
Terminal
symbols
Function
Description
P1/P1, P2/P0,
P3/P3, NC/P2
Input voltage
Connect the voltage input wire of the
measuring circuit.
Frame GND (FG) Connect to ground. (D-type ground)
MA, MB
Auxiliary power
Connect the auxiliary power supply.
1k, 1L, 2k, 2L,
3k, 3L
Input current
Connect the secondary output of the
current transformer (CT) connected to
the measurement circuit’s current wire.
485+, 485-
MODBUS
®
communication
Connect the communication wire
(MODBUS
®
RTU).
SLD
Connect to ground. (D-type ground)
Ter
Connect with “485-“ terminals (the unit
at end of the link)
X1, COM
X
Pulse input/
contact input
Connect pulse input/contact input
wires.
Y1, COM
Y
Pulse output/
contact output
Connect pulse output/contact output
wires.
Sign and function of the terminal block