![Mitsubishi Electric EMU4-FD1-MB User Manual Download Page 57](http://html.mh-extra.com/html/mitsubishi-electric/emu4-fd1-mb/emu4-fd1-mb_user-manual_239825057.webp)
(56/71)
Preset and all data reset
You can reset all the integrated measured values or some of them to zero. (such as electric energy, operating time, etc.)
・
The integrated measured values you can reset to zero are as follows:
Electric energy (consumption, regeneration), Reactive energy, Periodic energy, Pulse count, Equivalent CO
2
, Operation time
- Preset (Data reset of selected value)
・
In each integrated value display of operating mode, press both and at the same time for more than
two seconds to transition to preset mode.
・
Preset procedure is as follows:
- All data reset
・
In each integrated value display of operating mode, press both and at the same time for more than two
seconds to transition to all-data-reset display as below.
・
In all-data-reset display, choose “yES” to reset all the integrated values to zero, then back to the integrated value display.
・
In all-data-reset display, choose “no” to cancel resetting, then back to the integrated value display.
・
All data reset display transition
Operation of preset display
・
Press or to choose the value at flashing digit.
・
Press for the setting digit (flashing digit) to shift to lower.
・
Press for the setting digit (flashing digit) to shift to upper.
・
Press at the lowest digit to transition to preset confirmation display as below.
・
In preset confirmation display, choose ”yES” to reset value, then back to the integrated value display.
・
In preset confirmation display, choose ”no” to cancel resetting value, then back to the integrated value display.
・
Preset display transition example (Electric energy (consumption))
SET
DISP
+ / PHASE
- / RESET
SET
SET
- / RESET
+ / PHASE
+ / PHASE
SET
SET
SET
SET
SET
DISP
DISP
DISP
-
+
Integrated
value display
+
-
SET
SET
+
SET
+
Press both at the same
time for 2 sec
for 2 sec
-
+
+
DISP