How to use upper/lower limit alarm function
This device can set the upper/lower limit alarm value for each measured value individually.
<Monitoring items>
Upper limit alarm items Current demand, phase N current demand, Voltage, Electric power demand,
Power factor, Pulse count
Lower limit alarm items Current demand, Voltage, Electric power demand, Power factor,
<Alarm setting>
・
Upper limit value
Set the upper limit of measured value. For setting value and setting range,
・
Lower limit value
Set the lower limit of measured value. For setting value and setting range,
・
Alarm delay time
Set the value in case you want to remove the inrush current of the load, etc. from the objects of
monitoring. Alarm does not occur when the measured value goes below the upper limit or goes over
the lower limit within the configured time. For setting value and setting range,
page 27.
・
Alarm reset method
Alarm recovery operation is different according to the alarm reset method.
Reset method
Alarm recovery operation
Auto-reset (Auto) Reset the alarm automatically if the measured value goes below the upper
limit or goes over the lower limit.
Self-retention
(HoLd)
The alarm is held after the measured value goes below the upper limit or
goes over the lower limit. Alarm is cleared by alarm reset.
For setting,
page 27. For alarm reset operation,
<Alarm occurrence / recovery condition>
Alarm item
Alarm reset
method
Alarm status
Alarm occurrence / recovery condition
Current demand
Phase N current demand
Voltage
Electric power demand
Power factor
Auto-reset
(Auto)
Upper limit
monitoring
Occurrence
Measured value > configured upper limit
(Alarm delay time is available)
Recovery
Measured value
≤
configured upper limit
Lower limit
monitoring
Occurrence
Measured value < configured lower limit
(Alarm delay time is available)
Recovery
Measured value
≥
configured lower limit
Self-retention
(HoLd)
Upper limit
monitoring
Occurrence
Measured value > configured upper limit
(Alarm delay time is available)
Retention
Measured value
≤
configured upper limit
Recovery
Measured value
≤
configured upper limit
AND
Alarm reset
Lower limit
monitoring
Occurrence
Measured value < configured lower limit
(Alarm delay time is available)
Retention
Measured value
≥
configured lower limit
Recovery
Measured value
≥
configured lower limit
AND
Alarm reset
Pulse count
Auto-reset
(Auto)
Upper limit
monitoring
Occurrence
Measured value
≥
configured upper limit
Recovery
Measured value < configured upper limit
Self-retention
(HoLd)
Upper limit
monitoring
Occurrence
Measured value
≥
configured upper limit
Retention
Measured value < configured upper limit
Recovery
Measured value < configured upper limit
Caution: Measured value of pulse count is integrated, so you can reduce it (i.e. clear it to zero) by the preset operation of pulse
count only. For the preset operation of pulse count,
page 56.
<Alarm indication at alarm status>
No alarm
Alarm occurrence
Alarm retention
When indicating the
alarm-occurrence phase
When indicating
the other phase
When Indicating the
alarm-occurrence phase
When indicating
the other phase
Digital indication
Turn ON
Flash (*1)
Turn ON
Flash (*2)
Turn ON
Measured element,
Unit, Phase
Turn ON
Flash (*1)
Flash (*1)
Flash (*2)
Flash (*2)
*1: Flash (250ms ON / 250ms OFF) *2: Flash (500ms ON / 500ms OFF)