![Mitsubishi Electric EMU4-FD1-MB User Manual Download Page 11](http://html.mh-extra.com/html/mitsubishi-electric/emu4-fd1-mb/emu4-fd1-mb_user-manual_239825011.webp)
(10/71)
5. Procedure for wiring
Wiring for EMU4-FD1-MB
Rating voltage for every phase wire system
Phase wire type
Type
Rating voltage
Figure
3-phase 4-wire type
STAR
max AC277V(L-N)/480V(L-L)
Figure 1
3-phase 3-wire type
DELTA max AC220V(L-L)
Figure 2
STAR
max AC440V(L-L)
Figure 3
1-phase 3-wire type
―
max AC110V(L-N)/220V(L-L)
Figure 4
1-phase 2-wire type
(Note)
DELTA max AC220V(L-L)
Figure 5
STAR
max AC440V(L-L)
Figure 6
Note. In case of a circuit which is wired from the delta connection of a 3-phase 3-wire type, a circuit of a transformer of a
1-phase 2-wire type or a 1-phase 3-wire type, the maximum rating is “AC220V”.
In case of a circuit which is wired from a 3-phase 4-wire type or the star connection of a 3-phase 3-wire type, the
maximum rating is “AC440V”.