(52/71)
Measured item indication in operating mode
・
Indication of electric energy, reactive energy and periodic energy
- Indication format
The indication format of electric energy, reactive energy and periodic energy is as follows depending on the full load power:
*1: VT primary voltage in single-phase 3-wire system is regarded as 110V.
*2: Using direct connection, replace VT primary voltage with direct voltage in calculation above.
*3: In three-phase 4-wire system, replace VT primary voltage or direct voltage with phase voltage in calculation above.
Full load power
[kW]
Indication format
Digital indication
Unit
less than 12
8888.88
kWh
kvarh
12 or more
and less than 120
88888.8
120 or more and less than 1200
888888
1200 or more and less than 12000
8888.88
MWh
Mvarh
12000 or more
88888.8
・
Indication of electric power, power demand, reactive power and apparent power
- Indication format
The indication format of electric power, power demand, reactive power and apparent power is as follows depending on the
full load power:
(For the full load power, refer to above.)
Full load power
[kW]
Indication format
Digital indication
Unit
less than 12
888.888
kW
kvar
kVA
12 or more
and less than 120
8888.88
120 or more and less than 1200
88888.8
1200 or more and less than 12000
888888
12000 or more
8888.88
MW
Mvar
MVA
・
Indication of current and current demand
- Indication format
The indication style of current and current demand is as follows depending on the primary current:
Primary current
[A]
Indication format
Digital indication
Unit
less than 40
888.888
A
40 or more
and less than 400
8888.88
400 or more and less than 4000
88888.8
4000 or more
888888
・
Indication of voltage
- Indication style
The indication format of voltage is as follows depending on the primary voltage:
Primary voltage
[V]
Indication format
Digital indication
Unit
less than 300
88888.8
V
300 or more
888888
Caution: In three-phase 4-wire system, the indication of VT primary voltage and direct voltage depends on the phase
voltage.
α
:
1
Single-phase, 2-wire
2
Single-phase, 3-wire
√
3 Three-phase, 3-wire
3
Three-phase, 4-wire
Full load power [kW] =
α
x (VT primary voltage) x (CT primary current)
1000